4200FA Installation and Operation Manual
25
4.3
Power Connections 50 kVA
The following illustrates the wiring connections from the power distribution panel (not
part of the UPS) to the terminal block of the 50 kVA UPS Model
The Ground lugs are located to the left of TB4. See illustration, below.
Optional: Bypass Input: 3-phase, 3-wire
Optional: Bypass Input:
3-phase, 3-wire
208 V requires 3-phase,
4-wire
(H1) (H2) (H3) (N)
(H1) (H2) (H3) (N) (L1) (L2) (L3) (N) (+) (-)
OUTPUT: 3-phase (4-wire)
INPUT: 3-phase, 3-wire
208 V requires 3-phase,
4-wire
TB1
TB4
BATTERY
Ground Lugs (2)
Wire Capacity:
#14 – 1/0 AWG
TB4
TB1
50kVA with Back
Panel Removed