4200FA Installation and Operation Manual
4.1.2 Power Connections 15/25/30 kVA with Internal Transformer
The following illustrates the wiring connections from the power distribution panel (not part
of the UPS) to the terminal block of the 15/25/30 kVA UPS Models. (Maximum wire
capacity for TB1 and TB4 is 1 AWG.)
Ensure the three-phase commercial power input is connected for clockwise rotation. The
UPS output function is disabled if the input power is not phased for clockwise rotation.
* Customer-provided breaker for units with optional Bypass Input.
Optional Bypass Input:
3-Phase, 3-Wire
*208 V requires 3-Phase,
4-Wire Wye
TB4
INPUT GROUND RESISTANCE
LESS THAN 10 OHMS
CUSTOMER-PROVIDED AC DISTRIBUTION PANEL
TO BATTERY SYSTEM GND
TB1
Input Terminals: 1 – 5
Output Terminals: 6 – 10