Software description SRC-ADO
Thermokon Sensortechnik GmbH
Page 58
5.2 Digital output – “Sensor individual” e.g. Fan – output
If the fan stage should be output to the relays the function Sensor individual must be used
3 times for each stage.
Stage 1:
Data byte 3
Lower switch value [Bit] = 165
Upper switch value [Bit] = 185
Stage 2:
Data byte 3
Lower switch value [Bit] = 145
Upper switch value [Bit] = 165
Stage 3:
Data byte 3
Lower switch value [Bit] = 130
Upper switch value [Bit] = 145
Picture 5-3: Relay output – fan stages