Software description SRC-ADO
Thermokon Sensortechnik GmbH
Page 47
4.4.5 Sensor - Individual
In the output function “Sensor – Individual“ an EnOcean data byte of a sensor can switch a
digital output (On–Off).
Picture 4-22: Individual
4.4.5.1 Register Card Property
With sensor failure
o
Assignment of a defined value with sensor failure
o
Monitoring time amounts to 90 minutes
After-running time
o
Adjustable from 0 –65000 seconds
Selection data byte
o
Selection of data byte which should be effective on the output
o
Function of data byte can be found in the product data sheet of the manufacturer
Lower switch value and upper switch value
o
In the range between the lower and upper switch value, the relay is switched-on.
Example:
Temperature limiting value, sensor 0-40°C over 30°C, switch relay on:
Temperature of SR04 is inverted -> 0 °C = 255 bit and 40 °C = 0 bit
Selection data byte: data byte 1
Lower switch value: 0 bit
Upper switch value: 255 bit – (30 °C / 40 °C * 255 bit) = 64 bit