Software description SRC-ADO
Thermokon Sensortechnik GmbH
Page 38
4.4.1.1 Register Card Property
Sensor Property
Lower sensor measuring range/ Upper sensor measuring range
o
Enter measuring range of sensor
o
The measuring range can be found in the product data sheet of the sensor
Temperature-Offset
o
Adaption of temperature deviations of sensor
Set point adjustment (with SR04P.., SR04rHP.., SR07P… )
o
Manual adjustment of set point on the sensor
o
Range of –3/+3K and –5 / +5K and “None“ adjustable
With sensor failure
o
Assignment of a defined value with sensor failure
o
Monitoring time amounts to 90 minutes
o
With sensor failures window contacts are ignored after 90 minutes
o
If a sensor is transmitting again, the output is working normally again
o
Buttons are not monitored
General Controller Settings
Night lowering
o
Reduction of set point by none, 2 K, 4 K, 6 K, 8 K, 10 K, 12 K, antifreeze
protection
o
For night lowering the following can be used (OR-operation):
Room operating panel SR0x with slide switch
Digital module SR65DI
(lowering with opened contact e.g. with time switch)
Motion sensor
Wireless chair
Radio rocker / radio timer (PTM switch, Easyclick Timer)
Antifreeze protection (with activated energy stop)
o
Adjustable between 0 and 10 °C
o
For energy stop the following can be used:
Window contact SRW01
Window handle SecuSignal, SRG01
Lower Control Variable Limit
o
Selection whether the lower control variable limit shall be effective , if no
offset is existing.
o
Offset > 0
Lower control variable limit only becomes effective, if an offset is
existing
o
Offset = 0
Lower control variable limit is always effective, even if no offset is
existing.
Comfort Extension
o
The toggle between comfort operation into night lowering is made delayed by
the adjusted time (s). For example with the use of a wireless chair or a
motion sensor.