Software description SRC-ADO
Thermokon Sensortechnik GmbH
Page 39
Period
o
Time for pulse width modulation
Control Property
Basic-Set Point
o
Basic set point for control
Proportional range Xp
o
between 0-10 K adjustable
After-running time „Tn“
o
After-running time of integral range, adjustable from 0-255 min
o
If the after-running time „Tn“ is set to 0, the same is deactivated
Lower and upper control variable limit
o
Limitation of control output
Output
In the field “Output“ the current status of the output can be adjusted by activating
the hook mark
4.4.1.2 Register Card Sensors
1 Temperature sensor can be learned-in
Window contacts are “OR“- operated, i.e. all window contacts must be closed
If the window is opened the controller switches to 100% if the antifreeze
temperature was fallen below
Devices for night lowering are “OR“- operated
4.4.1.3 Changeover-Function
Changeover function is only on SRC-ADO-Type2 available. Changeover function is used
by 2-pipe Systems. Changeover between heating and cooling could be realized by using
micro switch (SR04/SR07 MS) or an extra digital input module (SR65-DI).