4.4.2 Controller – Two-Point Heating/Cooling Type1
Two Point is only available on SRC-ADO Type 1
Heating
With the two-point control the relay is switched-on if the set point is fallen below. If the set
point is exceeded, the relay is switched-off.
Cooling
With the two-point control the relay is switched-on if the set point is exceeded and
switched-off if the set point is fallen below.
With each new telegram received, the output quantity is recalculated. By the use of
window contacts the energy stop is activated if the window is opened. By the night
lowering, the set point can be lowered. The night lowering can be realized by the use of
SR65 DI, a slide switch respectively by a motion sensor. The devices for night lowering are
“OR-operated -> if one device is in night lowering when the controller is in night lowering.
Picture 4-18: Property Continuous Control