Software description SRC-ADO
Thermokon Sensortechnik GmbH
Page 53
4.4.10 Blind
In the output function “Blind“ a rocker can control a blind up and down. The function for the
blinds can only be selected on the outputs DO1 respectively DO3 in the main menu. The
outputs DO2 respectively DO4 are automatically be used for the blind function.
A rocker is effecting 2 relay outputs. The button ( ) affects output DO1 respectively DO3.
The button ( ) affects output DO2 respectively DO4. The outputs are locked against each
other by the software, so that always only one relay is switched.
4.4.10.1 Register Card Property
Long button actuation
o
Short button actuations are for the fine adjustment of the lamellas
o
A long button actuation starts the automatic run and controls the blind for the
running-after time continuously in the direction open respectively close.
o
The automatic run can be stopped by a renewed button actuation.
Output
o
In the field “Output“ the current status of the output can be displayed by
activating the hook mark.
4.4.10.2 Register Card Sensors
Number of sensors
o
Up to 15 buttons can be selected and assigned to the output
Picture 4-27: Blind