Software description SRC-ADO
Thermokon Sensortechnik GmbH
Page 44
4.4.3.1 Register Card Property
Sensor Property
Upon sensor failure
o
Assignment of defined value upon sensor failure
o
Monitoring time amounts to 90 minutes
General parameters
Value stage
o
Free definable value, by this value stage of FanCoil is set
Max. stage turn on time
o
FanCoils need for starting high voltage for run up
o
This value the time is set how long the FanCoil should run at start up in the
highest stage
Number of fan stages
o
Number of fan stages is chosen by the function in the main menu
Output
In the field “Output“ the current status of the output can be displayed by activating
the hook mark.
4.4.3.2 Register Card Sensors
1 temperature sensor can be learned-in
If the FanCoil should be connected to a controller, the same channel of the sensor
have to be chosen as it is used by the controller
Picture 4-20: Continuous FanCoil / PI Controller