15
COUNTERFLOW
CHAMBER RETAINER
F RONT F LUE MODELS SHOWN
SHOWN WI T H WARM AIR
OUT LET ON L EF T END
HORIZONTAL
OVERFIRE DRAFT
ACCESS COVER
OVERFIRE DRAFT
ACCESS PORT
NUT & WASHER
(4) PLACES
BURNER MOUNTING PLATE
BURNER MOUNTING
PLATE GASKET
COMBUSTION CHAMBER
CHAMBER RETAINER
OVERFIRE DRAFT
ACCESS COVER
OVERFIRE DRAFT
ACCESS PORT
NUT & WASHER
(4) PLACES
BURNER MOUNTING PLATE
BURNER MOUNTING
PLATE GASKET
CHAMBER RETAINER
COMBUSTION CHAMBER
chamber during shipping and helps to maintain insertion depth.
DO NOT remove
this retainer when installing burner. (Refer to Fig.3).
Fig. 3: Burner Mounting Plate for Counterflow and Horizontal Installations
When mounting the burner, (Fig 4) do not allow the burner tube or end cone to
physically touch or protrude into the chamber, as excess heat transfer could
result in destruction of the tube, end cone or both. The burner tube/end cone is
properly positioned, when the end is ¼ inch back from the inside surface of the
combustion chamber wall. A fiber insulating sleeve is provided with the Riello
BF3 Burner.
Fig. 4: Burner Insertion Illustration (Top view)
The oil burner provided with this furnace requires initial inspection, set-up, and
proper adjustment. Refer to this manual and the oil burner manufacturer’s
operating instructions for detailed information on the following items.
Initial firing of burner
Adjusting the burner combustion air
Adjusting the fuel pump pressure
Setting the draft control
Summary of Contents for OD6FA072D48
Page 32: ...31 APPENDIX B ELECTRICAL DIAGRAMS OD6 FAO72D48 NRGMAX CONTROL...
Page 33: ...32 OD6 FAO72DV5 NRGMAX CONTROL...
Page 34: ...33 OD6 FAO72D48 UT CONTROL...
Page 35: ...34 OD6 FAO72DV5 UT CONTROL...
Page 37: ...36 APPENDIX D REPLACEMENT PARTS OD6FA072D48 OD6FA072DV4...
Page 38: ...37...
Page 39: ...38 OD6RA072D48 OD6RA072DV4...
Page 40: ...39...
Page 41: ...40...
Page 42: ...41...
Page 43: ...42...