42
Battery Connection
NOTE: If the vehicle is equipped with a battery disconnect switch, always
wire the unit after the switch. This allows power to the unit to be turned
off by the battery disconnect switch.
1. Pass electrical wires CHA (black), 01, BAT and 2 (brown) to the
battery.
2. Using the recommended tools, cut the wires
to the proper length.
Do not coil or splice the excess wire.
3. Strip the wires and position the terminals supplied with the
recommended tools.
4. DISCONNECT THE CLAMP FROM THE BATTERY’S NEGATIVE
TERMINAL.
5. Connect wire 2 to one end of the fuse FP fuse holder (both supplied by
Thermo King) and connect the other end of the fuse holder to the
battery's positive pole. Install fuse FP (100A/12V or 60A/24V) in the
fuse holder. See note above.
6. Connect the *wire (wire between the battery and the vehicle starter
key) and the BAT wire to one end of the fuse F14 fuse holder (both
supplied by Thermo King), and connect the other end of the fuse holder
to the battery’s positive pole. Install fuse F14 (5A) in the fuse holder.
If F14 cannot be connected to the *wire, connect an additional fuse
(5A) between wire 01 and the vehicle starter key.
7. Connect the CHA wire to the clamp of the battery’s negative pole.
8. Reconnect the clamp of the battery’s negative terminal.
Summary of Contents for B-100-10
Page 9: ...9 Required Tools...
Page 13: ...13 Installing the Condenser Unit roof mounted ASA052 T 10 min...
Page 15: ...15 Installing the Condenser Unit roof mounted T 12 min...
Page 17: ...17 Installing the Condenser Unit front mounted T 10 min...
Page 19: ...19 Installing the Condenser Unit front mounted C T 15 min...
Page 21: ...21 Installing the ES100 Evaporator Unit T 20 min...
Page 23: ...23 Preparing Refrigeration Hoses T 10 min...
Page 25: ...25 Connecting Hoses to the Condenser Unit T 10 min...
Page 27: ...27 Connecting Hoses to the ES100 Evaporator T 14 min...
Page 29: ...29 Electrical Connections in the ES100 Evaporator T 10 min...
Page 31: ...31 Drain Circuit in the ES100 Evaporator T 5 min...
Page 33: ...33 Circuit Seal Test...
Page 35: ...35 In Case of Leaks 250 psig...
Page 37: ...37 Installing the In Cab Control 1 3 T 10 min...
Page 39: ...39 Optional Internal DIN Adaptor T 5 min...
Page 41: ...41 Control Cable Connection T 5 min...
Page 43: ...43 Battery Connection T 15 min...
Page 45: ...45 Fitting the Power Supply Units with Electric Standby T 10 min...
Page 47: ...47 Door Switch Connection DSW1 CHW T 1 min...
Page 49: ...49 Installing the Deflector T 5 min...
Page 51: ...51 Installing the Hose Covers T 12 min...
Page 57: ...57 Charging the Circuit...
Page 58: ...58 Outline Drawings...
Page 59: ...59 Outline Drawings...
Page 60: ...60 Outline Drawings...
Page 61: ...61...
Page 62: ...62...
Page 63: ...63...
Page 64: ...64...