OUTDOOR RESET MODE
Adjust the set-point temperature according to the outside temperature
This mode allows modulating the boiler output set-point temperature as a
function of the outdoor temperature. The outdoor temperature value comes
from a temperature sensor connected to the boiler controller.
If the outdoor sensor is not connected or if its circuit is open, an alarm signal
will be displayed on the display (SE). The boiler temperature set-point will
become the set value at
STPT Min T. Outdoor
.
Figure 15 : Outdoor reset curve
Table 10 :
OUTDOOR RESET MODE Settings
Display
BACnet Variable
Instance
Tag
Description
Parameters
Default
Calculated
SPTP
AV_TBoilerSTPT
CalculatedOUTR
ST
12
8388625
Current set-point temperature calculated based on
the adjustment curve and the outside temperature
10 to 93
0
C
50 to 200
0
F
---
STPT at Min
Outd T
WP_STPTatMinO
utdT
13
8388621
Boiler set-point temperature when the outside
temperature reaches the
Min Outd T.
10 to 93
0
C
50 to 200
0
F
140
0
F
STPT at
Max Outd T
WP_STPTatMax
OutdT
14
8388622
Boiler set-point temperature when the outside
temperature reaches the
Max Outd T.
10 to 93
0
C
50 to 200
0
F
80
0
F
Outdoor T.
AV_OutdoorT
2
8388610
Displays the outside temperature in real time when
the outdoor temperature sensor is properly
connected.
-46 to 107 °C
-50 to 250 °F
---
Min Outd T.
WP_MinOutdRst
T
15
8388623
Minimum outside temperature (Set to the area’s
coldest average temperature)
-46 to 107 °C
-50 to 250 °F
-10
0
F
Max Outd T.
WP_MaxOutdRst
T
16
8388624
Maximum outside temperature at which the
building will need heating
-46 to 107 °C
-50 to 250 °F
65
0
F