VOLTMAX ELECTRIC BOILER Installation and Operation Manual
(
Revised March 2019)
, Page
45.
MANUAL MODE
The maximum power is set manually.
Display
BACnet Variable
Instance
Tag
Description
Selection
Default
Current
authorized
max kW
WP_ManualCapL
imit
32
8388640
Configures the maximum electrical power that the
boiler will use.
0 to maximum rated
power
---
0-10 VDC MODE
An external 0-10 VDC controller is used to adjust the maximum power.
Display
BACnet Variable
Instance
Tag
Description
Selection
Default
Current
authorized
max power
(%)
AV_CapLimitPrc
54
8388662
The value of power (%) calculated based on the
current and the boiler’s nominal operating voltage 0 to maximum rated
power (%)
---
Minimum
Power Volt
(kW)
WP_MinRemote
VCapLimit
33
8388641
The boiler’s maximum power when the external
controller voltage is at
Min Voltage
0 to maximum rated
power
0
Maximum
Power Volt
(kW)
WP_MaxRemote
VCapLimit
34
8388642
The boiler’s maximum power when the external
controller voltage is at
V for max. cap.
0 to maximum rated
power
---
Current
Signal 0-
10V
AV_Remote010V
Cap
4
8388612
Voltage emitted by the external controller in real
time
0-10 V
---
Min Voltage
(VDC)
WP_CapLimitatM
inRemote010V
35
8388628
The voltage representing the external controller’s
minimum set-point
0-10 V
0
Max Voltage
(VDC)
WP_CapLimitatM
axRemote010V
36
8388629
The voltage representing the external controller’s
maximum set-point
0-10
10