![THERMO 2000 VoltMax105 Installation And Operation Manual Download Page 5](http://html.mh-extra.com/html/thermo-2000/voltmax105/voltmax105_installation-and-operation-manual_1104259005.webp)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual
(
Revised March 2019)
, Page
5.
Table 2 : VoltMax 480 VAC / 60 Hz / 3 Phases
1
Model
BTU/h
kW
Amps
Elements 480V
Stage
2
max. power
supply
(MCM)
3
VoltMax 192
655 104
192
231
8 x 15 kW
4 x 18 kW
4 x 48 kW
3 x 350
VoltMax 204
696 048
204
246
8 x 18 kW
4 x 15 kW
4 x 51 kW
3 x 500
VoltMax 225
767 700
225
271
15 x 15 kW
5 x 45 kW
3 x 500
VoltMax 240
818 880
240
289
10 x 15 kW
5 x 18 kW
5 x 48 kW
3 x 500
VoltMax 255
870 060
255
307
10 x 18 kW
5 x 15 kW
5 x 51 kW
3 x 500
VoltMax 288
982 656
288
347
12 x 15 kW
6 x 18 kW
6 x 48 kW
3 x600
VoltMax 306
1 044 072
306
368
12 x 18 kW
6 x 15 kW
6 x 51 kW
3 x600
VoltMax 315
1 074 780
315
379
21 x 15 kW
7 x 45 kW
6 x 300
VoltMax 336
1 146 432
336
405
14 x 15 kW
7 x 18 kW
7 x 48 kW
6 x 300
VoltMax 357
1 218 084
357
430
14 x 18 kW
7 x 15 kW
7 x 51 kW
6 x 300
VoltMax 384
1 310 208
384
462
16 x 15 kW
8 x 18 kW
8 x 48 kW
6 x 300
VoltMax 408
1 392 096
408
491
16 x 18 kW
8 x 15 kW
8 x 51 kW
6 x 500
1
Electrical supply 480 V 3 phase (L1-L2-L3) with 3 conductors Cu or AL ,90 °C with a ground.
2
The 45 kW stage is composed of three 15 kW elements.
The 48 kW stage is composed of two 15 kW elements and one 18 kW element.
The 51 kW stage is composed of one 15 kW element and two 18 kW elements.
3
-Maximum capacity of the boilers connection terminals
Table 3 : VoltMax 240 VAC / 60 Hz / 3 Phases
1
Model
BTU/h
kW
Amps Elements 240V
Stage
max. power
supply
(MCM)
2
VoltMax 105
358 260
105
253
7 x 15 kW
7 x 15 kW
3 x 500
VoltMax 120
409 440
120
289
8 x 15 kW
8 x 15 kW
3 x 500
VoltMax 126
429 912
126
303
7 X 18 kW
7 X 18 kW
3 x 500
VoltMax 144
491 328
144
347
8 x 18 kW
8 x 18 kW
3 x 500
1
Electrical supply 240 V 3 phase (L1-L2-L3) with 3 conductors Cu or AL ,90 °C with a ground.
2
-Maximum capacity of the boilers connection terminals
Table 4 : VoltMax 208 VAC / 60 Hz / 3 Phases
1
Model
BTU/h
kW
Amps
Elements 240V
2
Stage
max. power
supply
(MCM)
3
VoltMax 79
268 695
78,75
219
7 x 15 kW
7 x 11,25 kW
3 x 350
VoltMax 90
307 080
90
250
8 x 15 kW
8 x 11,25 kW
3 x 500
VoltMax 95
322 434
94,5
263
7 X 18 kW
7 X 13,5 kW
3 x 500
VoltMax 108
368 496
108
300
8 x 18 kW
8 x 13,5 kW
3 x 500
1
Electrical supply 208 V 3 phase (L1-L2-L3) with 3 conductors Cu or AL ,90 °C with a ground.
2
240V electrical element operated at 208V
3
-Maximum capacity of the boilers connection terminals