BI-ENERGY MODE
This mode selects the hydronic system heating source (VoltMax boiler or auxiliary boiler) using the
BI-E
terminal’s electrical switch. The benefit of this
mode is that the system can operate the back-up boiler when needed.
Display
BACnet variable
Instance
Tag
Description
Parameters
Default
Bi-Energy
Source
WP_SignalBiEne
rgy
47
20971567
Allows to select Bi-energy activation contact
source. BACnet or Local
Local
BACnet
Local
STPT
Source
WP_STPTSource
Aux
22
20971542
Selects the source used to control the set-point
temperature.
Auxiliary
means that the set-point will be
determined by the auxiliary boiler. The VoltMax
boiler has no set-point temperature and is only
used to activate the auxiliary boiler relay.
Voltmax
means that the set-point temperature will
be determined by the VoltMax boiler.
Auxiliary or
VoltMax
0 = Auxiliary
1 = VoltMax
VoltMax
Delta T.
Start Aux.
WP_DeltaTStartA
ux
44
8388652
This option adjusts the temperature differential
(Set-point temperature
– Water outlet temperature)
used to activate the auxiliary boiler.
0 to 55
0
C
0 to 100
0
F
20
0
F
Delta T.
Stop Aux.
WP_DeltaTStopA
ux
45
8388653
This option configures the temperature differential
(Set-point temperature
– Water outlet temperature)
in the VoltMax boiler used to deactivate the
auxiliary boiler.
0 to 55
0
C
0 to 100
0
F
5
0
F
Delay Start
Aux.
WP_DelayStartA
ux
46
8388654
This option adjusts the delay in minutes before
activating the auxiliary boiler.
Min
10