VOLTMAX ELECTRIC BOILER Installation and Operation Manual
(
Revised March 2019)
, Page
37.
BOOST MODE
Enable Boost Mode
This mode operates with the
Fixed Set-point
and
Outdoor reset mode
.
This menu allows the Boost mode to be activated,
this mode increase the set-point temperature
when the heating load of the building exceeds the
capacity generated by the current water
temperature determined by the boiler.
This mode is activated after a period of 30 min if
the heat demand is maintained for 30 consecutive
minutes on W1. After this period, the set
temperature will start to rise until a predetermined
maximum temperature is reached depending on
the heating mode until the demand is filled. This
temperature increase is temporary and has a
maximum duration of 120 minutes or when the
request is terminated on W1.
N.B. The
BOOST
mode is particularly interesting
for applications such as:
o
Applications with a programmable thermostat
with automatic lowering of the building
temperature.
o
Return to normal heat demand after a
prolonged period of sunshine where there
have been no long-term demands and,
therefore, heating floors will take a long time
to provide heat at d Normal water.
WARM WEATHER SHUTDOWN
Shuts down the boiler when the outside
temperature reaches an established
threshold.
This mode
stops the boiler’s heating production
when the outside temperature is higher than a
pre-determined temperature (ex: 68°F).
Note: If the boiler is configured with DHW mode,
it will continue to operate normally in order to
meet the DHW heating demand.
CHANGE PASSWORD
Changing the password
This menu allows you to change the installer
account password
ETHERNET
The settings available on the controller are also
available remotely on a web portal. This portal
works only when the boiler is properly connected
to an internet or Ethernet network. The various
setting parameters and the protocol for
connecting the boiler to a network are available in
the
Communication menu
and
Section 4.3.7
.
WEB PORTAL
In order to access the boiler remotely via the
internet, the boiler controller must be correctly
connected.
The web portal has 3 main menus, the
User
,
Installer
and
Manufacturer
menu. The structure
of the web portal is the same as the controller;
please refer to the previous sections, if you have
any questions.
Ex: The user can obtain information concerning
the boiler status, in the menu Operations /
N.B. The password to acces the installater
section of the website is 1111.
ALARM NOTIFICATION EMAIL
In order to configure the alarm by e-mail, you
must:
1. You must first ensure that you enter the
correct
information
in
the
controller
(depending on your network) under the
following options:
a. IP address
b. Default Gateway
c. Subnet mask
d. Primary DNS
e. Secondary DNS