VOLTMAX ELECTRIC BOILER Installation and Operation Manual
(
Revised March 2019)
, Page
48.
BACKUP MODE
Configures a second boiler as a backup.
Display
BACnet variable
Instance
Tag
Description
Parameters
Default
STPT
Source
WP_STPTSource
Aux
22
20971542
Selects the source used to control the set-point
temperature.
Auxiliary
means that the set-point will be
determined by the auxiliary boiler. The VoltMax
boiler therefore has no set-point temperature and is
only used to activate the auxiliary boiler relay.
Voltmax
means that the set-point temperature will
be determined by the VoltMax boiler.
Auxiliary or
VoltMax
0 = Auxilliary
1 = VoltMax
VoltMax
Delta T.
Start Aux.
WP_DeltaTStartA
ux
44
8388652
This option adjusts the temperature differential (set-
point temperature
– Water outlet temperature) used
to activate the auxiliary boiler.
0 to 55
0
C
0 to 100
0
F
20
0
F
Delta T.
Stop Aux.
WP_DeltaTStopA
ux
45
8388653
This option configures the temperature differential
(set-point temperature
– Water outlet temperature)
in the VoltMax boiler used to deactivate the
auxiliary boiler.
0 to 55
0
C
0 to 100
0
F
5
0
F
Delay Start
Aux.
WP_DelayStartA
ux
46
8388654
This option adjusts the delay before activating the
auxiliary boiler.
Min
10
EXTERNAL CONTACT MODE
This mode selects the hydronic system heating source (VoltMax boiler or auxiliary boiler) using the
BI-E
terminal’s electrical switch.
Display
BACnet Variable
Instance
Tag
Description
Settings
Default
STPT
Source
WP_STPTSource
Aux
22
20971542
Selects the source used to control the set-point
temperature.
External
means that the set-point will be
determined by the auxiliary boiler. The VoltMax
boiler therefore has no set-point temperature and is
used only to activate the auxiliary boiler’s relay.
Internal
means that the set-point temperature will
be determined by the VoltMax boiler.
External or
internal
Internal
MANUAL MODE
Manual mode is used to select the system’s operating mode (Electric or auxiliary).
Display
BACnet Variable
Instance
Tag
Description
Selection
Default
Active Boiler
WP_ActiveBoiler
23
20971543
This option selects which boiler is in operation;
either the VoltMax boiler (electric) or the auxiliary
boilder (auxiliary).
VoltMax ou
Auxiliary
0 = VoltMax
VoltMax