5.5
Alternative 3 (top)
For connection in the top "knockout holes". For this option, pipes are not included in the delivery.
min
1140 mm
min
1140 mm
420 mm
232 mm
251 mm
160°
90°
90°
Prepare the pipes according to the dimensions in the picture! Suitable choice is CU 28 mm intended for brine pipes.
32 mm
2, Insulate before mounting the pipes.
3, Press the pipes on to the connections in the heat pump (see picture below). Install the insulated pipes from the inside of the heat
pump and out. Pay attention to which one of the pipes are brine in and brine out (the pipe connections are located behind the electri-
cal cabinet in the heat pump, remove the metal plate). Isolate with insulation tape so that it is partially seated against the plate.
Brine IN
Brine OUT
4, Fit the rubber sleeves into the knockout
holes.
Installation Guide
Calibra Cool
Thermia AB
BWCC01IG0102
19