Product part no. 830049 Advantage
DC
Dual Zone Fire Control Panel
Manual part no 650.830049 rev. June 13, 2022
Field Wiring Specifications
Detection Circuits
Manual Release Circuit
Maximum length: 100’ each circuit
Maximum length: 100’ each circuit
Maximum linear resistance: 50 ohms
Maximum linear resistance: 50 ohms
Conductor cross section: 16-18 AWG
Conductor cross section: 16-18 AWG
Gold terminal contacts only
Gold terminal contacts only
IP67 sealed connectors
IP67 sealed connectors
Terminating End of Line: 470k ohms
Terminating End of Line: 470k ohms
Actuation Circuit
Pressure Switch Circuit
Maximum length: 100’ each circuit
Maximum length: 100’
Maximum linear resistance: 1 ohm
Maximum linear resistance: 50 ohms
Conductor cross section: 16-18 AWG
Conductor cross section: 16-18 AWG
Gold terminal contacts only
Gold terminal contacts only
IP67 sealed connectors
IP67 sealed connectors
Auxiliary Contacts
Pluggable Terminal Strips
Maximum Voltage
30 vdc
Conductor Cross Section
16-18 AWG
Current Rating
Normally Open = 1 amp
Normally Closed = ½ amp
Wire Terminal Torque
5 in-lb. (0.5 – 0.6 nm)
Wire Strip Length
0.275” (7 mm)
Mechanical Specifications
Enclosure
Dimensions
6.3” W x 8.6” L x 3.9” D
(152mm x 221mm x 107
)
System Normal
Green LED (flashing)
Weight
2.7 lbs. / (1.22 kg)
Fire Zone 1 & Zone 2
Red LED (flashing)
Service System - Fault
Yellow LED (flashing)
Battery Fault
Yellow LED (flashing)
Secondary Battery Circuit
Qty (1)
Alarm Silence
Yellow LED (flashing)
Local Audible Annunciator
Qty (1)
Environmental Specifications
Module Electronics
-40
o
F to 185
o
F
-40
o
C to +85
o
C
Enclosure Listed Ratings
UL 508
NEMA Type 4X
IP67
UL 94V-0
Secondary Backup
Power
-40
o
F to 185
o
F
-40
o
C to +85
o
C*
Battery life may be
affected at
temperatures above
+120
o
F (49
o
C)