Dual Zone Fire Control Panel
Manual part no 650.830049 rev. June 13, 2022
4.5 Fault Condition Operation
If a Fault condition occurs with any of the field wiring or internally supervised circuits, a
Fault condition is displayed on one of the front panel LEDs
Field wiring circuits include a minimum five second time delay before a Fault condition is
annunciated. If the Fault condition resets to Normal before the five second delay times
out, no Fault will be annunciated, or event logged.
All Alarm and Fault conditions are annunciated via an LED flash code sequence. The
flash code displayed by the Service System LED and corresponds to the indicated zone
and condition I.D. The flash code list is printed on the front panel label of the
Advantage
DC
electronics module.
Press and hold the Push to Test button to read the diagnostic flash code.
Diagnostic flash codes are as follows:
Service System
Flash Code
Description
1X
Detection Zone 1
2X
Detection Zone 2
3X
Manual Release Zone
4X
Actuation Zone 1
5X
Actuation Zone 2
6X
Auxiliary Switch
7X
Actuation Disable
8X
Local Buzzer
9X
Ground Fault
10X
Abort Switch Fault
11X
Cross Zone Fault
12X
Temperature Fault
Other LED Indicators
Description
Battery Fault
Battery Fault