Product part no. 830049 Advantage
DC
Dual Zone Fire Control Panel
Manual part no 650.830049 rev. June 13, 2022
from 0 to 30 seconds via offline PC or SmartDevice programming. Output control
contacts control may be mapped to individual detection inputs. Both sets of relay
contacts may be programmed for momentary transfer by pressing the front panel Reset
Switch. This function may be used for interrupting power to latching function initiating
devices (latching relay base smoke detectors). All I/O contact ratings are ½ amp at 30
VDC.
•
Relays 1 & 2 – Normally Closed/Common & Normally Open/Common
•
Relay 3 – Normally Closed/Common
•
Fire Alarm Control Panel (FACP) Fault – Fire Relay Contacts
Local Audible Buzzer Operation
A supervised local piezo buzzer is located on the control panel front cover. The buzzer
provides an audible alarm in the event of a Fire or Fault condition. A push button is
located on the inside of the control panel, which may be used to silence the audible
alarm. An LED indicator illuminates when the silence enable function is operated. The
silenced audible alarm will turn On if the Fire or Fault condition has not been cleared
AND after the audible has been silenced for six hours OR if a new Fault or Alarm
condition is detected. The alarm silence function cannot be engaged prior to an alarm
condition.
LED Visual Annunciation Operation
Visual LED indications are visible through a window on the hinged front cover. LED
indications are visible for:
•
System Normal (green)
•
Fire Alarm Detection Zone 1 (red)
•
Fire Alarm Detection Zone 2 (red)
•
Manual Release Fire Alarm (red)
•
Fault Condition Service System LED (yellow)
•
Battery Fault LED (yellow)
•
Alarm Silence LED (yellow)
A key lock position is provided to prevent access and tampering to internal components
by unauthorized individuals. Upon opening the front cover, the Alarm Silence, System
Reset, Push-to-Test push buttons, and System Disable toggle switches may be
accessed.
The Alarm Silence push button only active when the audible alarm is ON. The audible
alarm cannot be pre-silenced.
The System Reset push button will clear all latched alarms and latched relay outputs
once the circuit causing the Alarm condition has been cleared and returned to Normal
Operation.
The Push-to-Test button will illuminate all LEDs and sound the audible alarm but will not
transfer relays.