Product part no. 830049 Advantage
DC
Dual Zone Fire Control Panel
Manual part no 650.830049 rev. June 13, 2022
4.3 Advantage
DC
Default Settings
The Advantage
DC
allows for a variety of programming options as described in section 7.
The Advantage
DC
default settings for detection, actuation and relay operation are as
follows:
Advantage
DC
Default Configuration
Detection Zone
Enabled? Actuation Zone Delay
Zone 1
Yes
1
0
Zone 2
Yes
2
0
Manual Release
Yes
Both
0
Auxiliary Input
No
N/A
N/A
Abort Switch
No
N/A
N/A
Relay 1
Yes
Any Alarm
0
Relay 2
Yes
Any Alarm
0
Relay 3
Yes
Any Alarm
0
FACP Fault Relay
Yes
Any Fault
5
FACP Fire Relay
Yes
Any Alarm
0
4.4 Alarm Condition Operation
If an Alarm condition occurs on any automatic detection zone,
•
The green System Normal LED will turn OFF,
•
The buzzer will begin to pulse,
•
The alarm zone will be indicated by the Alarm Zone red LED flashing ON,
•
Depending on detection-actuation mapping, the mapped actuation zone
will fire,
•
Depending on actuation-relay mapping, the mapped relay(s) will transfer,
•
The sequence of events (Fire by zone, Actuation by zone, etc.) are
recorded, and time stamped in the Event Log
If the manual release circuit is initiated,
•
The green System Normal LED will turn OFF,
•
The buzzer will begin to pulse,
•
Both alarm zones will be indicated by the Alarm Zone red LED flashing
ON,
•
Depending on detection-actuation mapping, the mapped actuation zones
will fire,
•
Depending on actuation-relay mapping, the mapped relay(s) will transfer,
•
The sequence of events (Fire by zone, Manual Release, Alarm Silence,
etc.) are recorded, and time stamped in the Event Log