![TFC AdvantageDC Product Operation And Maintenance Procedure Download Page 28](http://html1.mh-extra.com/html/tfc/advantagedc/advantagedc_product-operation-and-maintenance-procedure_1098942028.webp)
Product part no. 830049 Advantage
DC
Dual Zone Fire Control Panel
Manual part no 650.830049 rev. June 13, 2022
6.0 Advantage
DC
Troubleshooting and Customer Support Info
6.1 Diagnostic Guide
•
Before performing diagnostics, ensure the system will not discharge accidentally
•
Check all connections before replacing components. Look for broken wires, loose or
broken connectors and pin/socket connections
•
Look for evidence of corrosion on connectors, pins and sockets
•
Check for connectors not completely engaged and pin/sockets not completely inserted
into connectors
•
Keep in mind that a fault condition will not show up as a service system flash code until
five continuous seconds. Power failure will not be indicated until 20 seconds
•
If a multimeter is used to check circuit voltage, continuity, or resistance, ensure the
meter settings will not cause firing of the actuation circuit