Product part no. 830049 Advantage
DC
Dual Zone Fire Control Panel
Manual part no 650.830049 rev. June 13, 2022
4.8 Detection, Actuation & Relay Operation
Definitions
Cross-Zoned Alarm – Cross-zoning requires one detector on each of two separate zones
to be in an Alarm condition before actuation is engaged. A single sensor in alarm causes
a Fault condition on the panel. See the following tables for actuation and relay mapping.
Mapping – Logical connection between an initiating (detection) zone, an actuation zone
and I/O relay operation performed by programming the Advantage
DC
via the user PC and
interface module.
Momentary Transfer – A relay option which allows for a one-second transfer when the
control panel System Reset button is pressed. Used for resetting smoke detectors.
Single Detection Alarm – Any single detection zone alarm will cause the mapped actuation
zone to fire.
Detection-Actuation Mapping Options
Detection Zone
Actuation Zone
(select one)
Discharge Delay
Zone 1
1
0 – 30 5 second increments
“
Discharge Both Zones
“
Zone 2
None
N/A
“
1
0 – 30 5 second increments
“
2
“
“
Both zones
“
Cross-Zone Detection
Zones 1 & 2
Cross zone enabled
“
Manual Pull
All enabled zones
0 – 30 5 second increments