Product part no. 830049 Advantage
DC
Dual Zone Fire Control Panel
Manual part no 650.830049 rev. June 13, 2022
The following programming options for detection, actuation and relay mapping may be accessed
by offline programming of the Advantage
DC
using a PC utility software and interface device or
Bluetooth interface module. Refer to Section 7 System Programming for detailed instructions to
change the default settings.
Fire and Fault Condition Relay Mapping Options
Relay
Default
(sec)
Delay
(sec)
Relay Operation Mapping Options
Relay 1
0
0 – 30 Transfer on single zone alarm
“ “
“ “
“ “
Transfer on cross zone alarm
“ “
“ “
Transfer on fault condition
Relay 2
0
0 – 30 Transfer on single detection alarm
“ “
“ “
“ “
Transfer on cross-zoning detection alarm
“ “
“ “
Transfer on fault condition
“ “
“ “
Follows function of local audible - Silenceable
Relay 3
0
0
Transfer on single detection alarm
“ “
“ “
“ “
Transfer on cross-zoning detection alarm
“ “
“ “
“ “
Momentary transfer when Reset button is pressed
FACP Fault Relay
5
0 – 30 Transfer on any Fault
FACP Fire Relay
0
0 - 30
Transfer on single detection fire alarm
“ “
“
“ “
Transfer on cross-zoning detection alarm
Advantage
DC
Relay Default Settings
Relay
Normal
Operation
Single Fire
Alarm
Dual Fire Alarm
(Cross Zoning)
Fault
Condition
Momentary Transfer
with Reset Button
1
Off
On
On
Off
Yes
2
Off
On
On
Off
Yes
3
Off
On
On
Off
Yes
Alarm
Relay
Off
On
On
Off
Yes
Fault
Relay
On
On
On
Off
No
Notes
1) The FACP Fault Relay is normally On and turns Off in the event of any system fault.
2) The FACP Fault Relay may be programmed for a Power Failure Fault delay of up to
180 minutes. This allows for a temporary power failure to be ignored by the
Advantage
DC
control panel.