Important InformatIon about thIs manual
© TESVOLT We reserve the right to make technical changes! RD.TI.026.E.ENG_Installation_Manual_TSHV70OD_v.B.01 Last revised 01/2021
1.4 LIMITATION OF LIABILITY
TESVOLT GmbH assumes no liability for personal injury, damage to property, damage to the product
and follow-on damage attributable to the following causes:
•
Non-compliance with this manual,
•
Improper use of the product,
•
Repairs, opening the cabinet and other actions performed on or with the product by unauthorised
and/or unqualified personnel,
•
Use of non-approved spare parts.
Unauthorised modifications or technical changes to the product are forbidden
1.5 APPROPRIATE USE
The TESVOLT TS HV 70 Outdoor is a modular battery storage system based on lithium-ion technology.
The components were built in accordance with the current state of the art in technology and prod-
uct-specific standards.
The TESVOLT TS HV 70 Outdoor has been designed for operation with the Sunny Tripower Storage 60
(SMA STPS 60) three-phase battery inverter manufactured by SMA. Any other use must be agreed
with the manufacturer and, if necessary, with the local energy supply company.
It may be operated outdoors or indoors. Depending on the variant and design, the
TESVOLT TS HV 70 Outdoor works within an ambient temperature range of -33°C to 55°C and at a maxi-
mum humidity of 85%. The battery cabinet may not be exposed to corrosive environments.
When installing the battery storage system, ensure that it is standing on a sufficiently dry, horizontal
and flat surface with sufficient load-bearing capacity. The inclination of the installation area may not
exceed 0.5%. Irregularities must be < 0.25% in accordance with DIN 18202. The system is to be installed
in the agreed location and may not be subsequently moved. The altitude of the installation location may
not be higher than 2,000 m above sea level without approval in writing from the manufacturer.
In regions subject to flooding or in topographical depressions, care must be taken to ensure that the
battery storage system is installed in a suitably elevated location and is protected against contact with
water.
The outdoor cabinet may not be installed in the immediate vicinity of fire loads.
Furthermore, a risk assessment in accordance with DIN EN 62305-2 is required for the installation site
to assess the lightning protection measures and, if necessary, to install lightning protection.
Care must be taken at the installation site to ensure that external mechanical loading (e.g. from being
driven into by vehicles or from falling trees) cannot occur.
Adherence to the specifications in this manual also forms part of appropriate use.
The TESVOLT TS HV 70 Outdoor may not be used:
•
For mobile use on land or in the air (it may only be used on water in agreement with, and with the
written consent of, the manufacturer),
•
For use with medical equipment,
•
As a UPS system.
1.6 GUARANTEE
The current guarantee conditions can be downloaded from the internet by visiting
www.tesvolt.com
.