![TESVOLT TS HV70 Outdoor Installation And Operating Manual Download Page 26](http://html1.mh-extra.com/html/tesvolt/ts-hv70-outdoor/ts-hv70-outdoor_installation-and-operating-manual_1092604026.webp)
26
InstallatIon
© TESVOLT We reserve the right to make technical changes! RD.TI.026.E.ENG_Installation_Manual_TSHV70OD_v.B.01 Last revised 01/2021
6.2 CONNECTING THE EXTERNAL CABLING
WARNING! Risk of damage to the battery cabinet
Do not under any circumstances step on the base cover or use it as a support. The base cover is easily
deformed, which can lead to damage. If necessary, use the frame of the battery cabinet as a support
with due care and attention.
1
Remove the cover of the floor outlet. To do this, loosen the 5.5 x12
screws using a TX30 Torx screwdriver.
2
Feed all the cables for connecting the TS HV 70 Outdoor through
the floor outlet.
The cables must extend beyond the floor outlet by the following
lengths:
Network cable (Janitza power measurement/internet): 1.40 m
Grounding rods/
foundation grounding connection: (1 x ≥50 mm
2
)
1.10 m
AC supply line (5 x 50 mm²):
0.75 m
3
Feed all the cables through the seal on the cable outlet cover.
4
Feed the cables through the cover. The cover must not be fas-
tened yet.
5
Remove the connector panel cover
D
. Feed the AC cable under-
neath the heating unit up to the connector panel. Lay the AC cable
on the through clamps
39
in accordance with the instructions in
section “5.8 Connector panel” on page 19 et seq.
STOP