background image

ISU-689:2016/GB 

 

 

 
3.6. Selection of expansion vessel  

 

The boiler is not equipped with an expansion vessel, the vessel must 
be mounted on the installation. In installation with additional 
hydraulic coupling or plate heat exchanger, an individual expansion 
vessel should be installed in the boiler

’s

 circuit. A proper expansion 

vessel should be selected by the designer of central heating system. 
Installation of expansion vessel should be made by an installation 
contractor in accordance with applicable regulations.  

 

3.7. Condensate outlet  

 
Each boiler has a condensate drainage system installed and already 
connected.  
The flexible pipe for condensate drainage must be connected to the 
condensate collection and removal system in accordance with the 
applicable regulations. The designer, considering the power of the 
installation and the utility of the building, should adapt the system to 
neutralization of the resulting condensate. The condensate drain 
installation must be made of corrosion-resistant material. 

 

The installation should be carried out in a way that prevents the 
condensate from freezing. Check the condensate drain before 
starting.

 

The connection of drain the condensation water cannot be 

blocked. 

 

The bottom of the siphon (2) was dismantled during transport. All 
parts necessary for installation: 1-gasket, 2-bottom of siphon, 3-nut, 
are in the package of the boiler. Before starting the boiler, the siphon 
should be assembled in accordance with Fig. 3.7.1. 

 

 

Fig. 3.7.1 

 Mounting the siphon

 

 

Before the start-up of the boiler move the siphon to the 
lowest position, to enable the hose (which connect heat 
exchanger with siphon) to a proper condensate outlet 

                   (see the Fig. below). A bent hose may cause the flooding of 
                   heat exchanger by produced condensate.   

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

During the start-up or after a long downtime, make sure that the 
condensate is properly drained through the drain (E) see Fig 3.4.1.  

 

 

3.8. Flue gas outlet 

 
Flue gas outlet from the boiler must be made in accordance with 
applicable regulations and this instruction manual and it needs to be 
agreed with the district chimney sweep service company.  

 

For flue systems, the boiler is made according to type: C13, C33, C43, 
C63, B23. 

 

 

it has closed combustion chamber in relation to the room where it 
is installed (C), 

 

is adjusted to be connected to separately approved and marketed 
air-flue gas systems, 

 

it is equipped with a blowing fan (3).

 

 

The boiler is designed for cooperation with the flue gas 

 air system 

with a diameter of  

Φ

 100 (flue gas and air) and in a collective 

cascade system where the flue gas exhaust from a single boiler is 
realized by a pipe with diameter of 

Φ

 100. To install the flue gas 

 air 

system to the boiler, it is recommended to mount the flue gas 
adapters according to this manual, the adapters are supplied with 
the boiler and are added to the boiler

’s

 package.  

 

Other components of the flue gas 

 air system of the boiler should be 

purchased according to the design of the installation.

 

 

The boiler is factory adjusted with mounted exhaust 
pipe 

Φ

100 of the maximum length 0,5m without air 

pipe. Settings CO

2

 

 9% for natural gas. To use the other 

                  systems and longer pipes it is required to adjust the 
                  boiler as specified in point 4.3. 

 

 

Connections and chimney duct must be designed and constructed in 
accordance with applicable regulations. They must be made of 
suitable material. They also must be corrosion-resistant, smooth 
inside and tight, impervious to condensate. 

 

 

Use the appropriate wire size (diameter, maximum length, resistance 
on the knees), depending on the combustion system used. The 
dimensions of the wires should be adequately compatible as given in 
table. Resistance of flue gas flow on each elbow depending on the 
bending angle and related reduction of the maximum wire length are 
given in section 3.8.2. 

 

Connection of the boiler to the air-flue gas system and installation of 
the system itself should be sealed. Each system should be installed 
with the windproof outlet protecting against external factors. 

 

Before turning on the boiler check if flue-gas system is made 
according to the project and air- and flue ducts lengths are shorter 
than maximum lengths showed in above tables. Make sure flue-gas 
system is tight.  

 

After turning on the boiler check if it operates correctly. Also check 
combustion parameters by checking concentration of CO

2

 and/or O

2

 

in flue-gas. 

3.8.1. Configuration Type B with open chamber and forced 
draft  

 

The air is sucked directly from the environment in which the boiler is 
installed through the hole made in the boiler

’s

 top cover. The 

exhaust outlet should be connected to your own single chimney or 
directed directly to the outside of the building according to the 
requirements of applicable regulations. 

 

Boilers with open combustion chamber type B can not be installed in 
rooms exposed to vapors or volatile substances (e.g. vapors of acids, 
paints, adhesives, solvents, fuels, etc.), as well as areas dusty with 
wood, coal, cement, etc. 

 

Summary of Contents for ECOCONDENS CRYSTAL 100

Page 1: ...INSTRUCTION MANUAL INSTALLATION OPERATION AND MAINTENANCE Gas fired condensing central heating boilers SYSTEM BOILERS ECOCONDENS CRYSTAL 80 ECOCONDENS CRYSTAL 100...

Page 2: ...lters are not included in a basic boiler equipment An example of connecting a boiler to these systems is presented on fig 3 5 1 All defects caused by lack of filters on central heating or gas supply w...

Page 3: ...nnecting the boilers in the cascade system 10 4 BOILER ADJUSTMENT AND PRELIMINARY SETTING 10 4 1 INTRODUCTORY REMARKS 10 4 2 ADJUSTING THE BOILER TO COMBUST ANOTHER TYPE OF GAS 11 BOILER CAN BE ADJUST...

Page 4: ...esign and technical specifications of the boiler 2 2 1 Main units of the boiler 2 1 Flue gas water heat exchanger 2 2 Temperature limiter of flue gas 2 3 Temperature limiter of air collector 2 4 Ignit...

Page 5: ...parameter P06 If the heating water temperature exceeds 97 C an additional temperature limiter is activated the burner is turned off until the hot water temperature drops below 81 C The system of conti...

Page 6: ...he boiler from the SUMMER function CH only to the WINTER function CH and DHW A 3sec The entrance to the TEST mode B The reset the displayed error B 3sec Preview of the parameters C Turns on or off the...

Page 7: ...This prepared cables connect according to Fig 3 1 3 1 Fig 3 1 3 1 Wire colors L brown N blue PE yellow green If you need to replace the supply wire use a minimum cord of 3 x 0 75 mm2 The boiler supply...

Page 8: ...ing the back and bottom of the boiler Due to the heavy weight 2 people are required Fig 3 3 1 Mounting dimensions Mounting method on hooks Mounting method with hanger Fig 3 3 2 Mounting method Fig 3 3...

Page 9: ...n are not used as grounding the electrical installation Connect the outlet of safety valves to the floor drain to avoid flooding the room where the boiler is installed as a result of protection device...

Page 10: ...a blowing fan 3 The boiler is designed for cooperation with the flue gas air system with a diameter of 100 flue gas and air and in a collective cascade system where the flue gas exhaust from a single...

Page 11: ...he sum of the lengths of the flue gas air system when the elbow is mounted on the flue gas system or the air supply system to the boiler Table 3 8 3 1 Reduce the length of the installation elbows Exam...

Page 12: ...iler connection with PC MASTER and SLAVE communication connectors are not located in the control console casing Connectors appropriately described are located in bulk inside the boiler Fig 3 9 1 1 Des...

Page 13: ...r in tank EP External cascade pump ES Outdoor temperature sensor CS Temperature sensor in supply collector 3W three way valve Boilers cooperating in the cascade system are connected in series by a cab...

Page 14: ...ctrical installation was made in accordance with applicable regulations the correctness of connections between the boiler and the chimney was checked and confirmed by a qualified chimney service 4 3 B...

Page 15: ...mming mode is switched off 4 5 1 Preview of parameters value You can review the parameter values without the need of change To do this use the B 3sec button After starting LOCAL INSTALLATION mode the...

Page 16: ...ow pressure fill the installation with a filling valve mounted on the installation Start the boiler in the TEST service mode the boiler will start the circulation pump and start the ignition Due to la...

Page 17: ...de The symbol W11 shown on the picture will appear on the screen Press B button to activate the boiler 5 4 Diagnosis When the operation of the boiler will be incorrect the display shows the symbol E a...

Page 18: ...ctrical connections Error 96 description When the P14 parameter is set on a value other than zero the controller does not detect the presence of the sensor closed open Please check the sensor ES conne...

Page 19: ...ont cover 1 Loosen the screws K1 2 Pull the cover behind its lower edge to release from the latches 3 Move the cover up Dismantling the side cover 4 Unscrew the screws K2 5 Move the cover up Fig 6 1 1...

Page 20: ...gas 6 1 3 Thermal protection of the heat exchanger The heat exchanger is equipped with thermal protection BW1 and BW2 protecting against improper assembly of the exchanger If the exchanger is mounted...

Page 21: ...ceeding the limits of temperature protection against exceeding the pressure limits check whether vents are present with correct dimensions and operating according to the installed device In this regar...

Page 22: ...ELV Contact Thermal fuse item 2 2 Supply voltage from the controller SELV Activation temperature 115 C Return NTC sensor item 2 14 Supply item 2 15 Supply voltage from the controller SELV 12K 25 C 363...

Page 23: ...e the power level with D and E buttons by 1 use F button to set the min power or G button to set the max power The PWM signal for the cascade pump is selected according to the operation algorithm of b...

Page 24: ...g 7 2 3 2 1 Diagram of connecting boilers for DHW needs in divided configuration with one three way valve Diagram of connecting 4 boilers two of which are intended for heating DHW Each boiler is equip...

Page 25: ...E n v i r o n m e n t a l p r o t e c t i o n Emission of NOx natural gas Class Class NOx 6 Emissions of nitrogen oxides mg KWh 50 The pH of the condensate natural gas 5 Max amount of condensate natu...

Page 26: ...ly H Flue gas temperature limiter RELAY Relay of the pump 5A ALARM Error information connector PWM PWM pump control G1 Protection against heat exchanger overheating 2xF2 5A Fuses in control panel RT T...

Page 27: ......

Page 28: ......

Reviews: