Service and Repair Manual
April 2021
Control System Fault Codes
126
S
®
-60/65 XC
™
• S
®
-60/65
HF • S
®
-60/65 TraX
™
Part No. 1288652GT
ID Component ID Name
Cause
Effect
Solution
12 Machine
CAN Bus
13 Not
detected
Machine CANBUS
CAN+ or CAN-
shorted to supply
Machine will not be
functional.
*Verify with a voltmeter that CAN+
and CAN- lines are not shorted.
*Measure the resistance between
(YL, TCON J5-3) and
D81CAN- (GR, TCON J5-4); should
be between 55 and 65 ohms.
* (YL, TCON J5-3) should
be between 1V and 5V.
*D81CAN- (GR, TCON J5-4) should
be between 1V and 5V.
*Remove short(s) and cycle power.
13 Jib
Up/Down
Switch
27 Active at
startup
Toggle switch input
was detected as
HIGH at start-up.
The Jib Up or Down
functions will not
operate.
*Verify with a voltmeter that the Jib
Up/Down Toggle Switch (TS8) is
operating properly.
* C43JU (BL, PCON J17-6) should be
0 V with the switch OFF and 12 V with
the switch held in the UP position.
* C44JD (BL/BK, PCON J17-8)
should be 0 V with the switch OFF
and 12 V with the switch held in the
DOWN position.
*Cycle power to allow the machine to
re-test the fault.
15 Foot Switch 27 Active at
startup
Foot switch input
was detected as
HIGH at start-up,
or the footswitch
was held for too
long and caused
the footswitch timer
to elapse.
Machine will not be
functional.
* Release foot switch and cycle
power.
* If problem persists, with a voltmeter
verify that C24FS (WH, PCON J12-2)
is LOW when foot switch is released
and 12 V when held down.
28 Timeout Foot switch
depressed too long
without action
Machine will not be
functional.
17 Aux Pump
Coil
11 Shorted
to
supply
voltage
TCON detected
that C27AUX
circuit is shorted to
12V.
Machine will not be
functional.
*Check C27AUX (RD, TCON J3-3)
wiring. *With a voltmeter verify that
C27AUX (RD, TCON J3-3) is 0 V
when the Auxiliary Power toggle
switch is OFF and 12 V when switch
is ON.
*Verify the terminals of the APU
solenoid have a resistance greater
than 5 ohms. If not, replace the
solenoid.
19 Aux Enable
Switch
27 Active at
startup
Aux button held at
startup.
Machine will not be
functional.
Release Aux button, check DISCON
overlay and ribbon cable if issue
persists.
Summary of Contents for Genie S-60 HF
Page 195: ...April 2021 Service and Repair Manual 183 Electrical Schematic Deutz TD 2 2 L3 Models ...
Page 198: ...Service and Repair Manual April 2021 186 Electrical Schematic Deutz TD 2 2 L3 Engine Harness ...
Page 199: ...April 2021 Service and Repair Manual 187 Electrical Schematic Deutz D 2 9 L4 Models ...
Page 203: ...April 2021 Service and Repair Manual 191 Electrical Schematic Perkins 404F E22T Models ...
Page 206: ...Service and Repair Manual April 2021 194 Electrical Schematic Perkins 404D 22 Models ...
Page 207: ...April 2021 Service and Repair Manual 195 Electrical Schematic Ford MSG 425 EFI Models ...
Page 210: ...Service and Repair Manual April 2021 198 Electrical Schematic Generators ...
Page 217: ......