April 2021
Service and Repair Manual
Control System Fault Codes
Part No. 1288652GT
S
®
-60/65 XC
™
• S
®
-60/65
HF • S
®
-60/65 TraX
™
113
ID Component ID Name
Cause
Effect
Solution
41 Turntable
Rotate
Joystick
12 Joystick
voltage too
high.
Circuit C165TTR
is above 4.5 V.
Turntable
Rotate
functions will
not operate.
* Leave joystick in neutral position and
cycle power.
* If fault persists, with a voltmeter check
that C165TTR (WH/RD, PCON J18-2) is
at 2. 5V +/- 0.2 V at startup and does not
go above 4.5 V or below 0.5 V when fully
stroked in each direction.
* Replace joystick if voltage check fails.
15 Joystick
voltage too
low.
Circuit C165TTR
is below 0.5 V.
19 Joystick
held at
startup.
Circuit C165TTR
voltage was not
within the startup
voltage range of
2.5 V +/- 0.2 V.
42 Turntable
Rotate CW
Valve
12 Circuit
shorted to
V+
TCON detected
that C4TRL
circuit is shorted
to 12 V.
Turntable
Rotate
functions will
not operate.
* With a voltmeter, measure Y24.
Proper resistance should be between 5 -
60 ohms. Replace Y24 if resistance is
outside of those values.
* Verify wiring for C4TRL (WH, TCON J3-
12) and check for open or short circuits.
15 Circuit
shorted to
GND
TCON detected
that C4TRL
circuit is shorted
to GND.
43 Turntable
Rotate CCW
Valve
12 Circuit
shorted to
V+
TCON detected
that C5TRR
circuit is shorted
to 12 V.
Turntable
Rotate
functions will
not operate.
* With a voltmeter, measure Y23.
Proper resistance should be between 5 -
60 ohms. Replace Y23 if resistance is
outside of those values.
* Verify wiring for C5TRR (WH/BK, TCON
J3-1) and check for open or short circuits.
15 Circuit
shorted to
GND
TCON detected
that C5TRR
circuit is shorted
to GND.
44 Drive Enable
Switch
19 Stuck ON
at power
up.
Toggle switch
input was
detected as
HIGH at start-up.
Drive Enable
switch will
not operate,
possibly
preventing
drive while
the turntable
is rotated.
Verify with a voltmeter that the Drive
Enable Toggle Switch (TS15) is operating
properly.
* C143DEL (BL/RD, PCON J16-7) should
be 0 V with the switch OFF and 12 V with
the switch held in the ON position.
Cycle power to allow the machine to re-
test the fault.
45 Platform
Level
Up/Down
Switch
19 Stuck ON
at power
up.
Toggle switch
input was
detected as
HIGH at start-up.
Platform
Level Up or
Down
functions
may not
operate,
depending
on which
direction the
switch fault
occurred.
Verify with a voltmeter that the Platform
Level Up/Down Toggle Switch (TS9) is
operating properly.
* C14PLU (OR, PCON J17-2) should be 0
V with the switch OFF and 12 V with the
switch held in the UP position.
* C15PLD (OR/BK, PCON J17-3) should
be 0 V with the switch OFF and 12 V with
the switch held in the DOWN position.
Cycle power to allow the machine to re-
test the fault.
Summary of Contents for Genie S-60 HF
Page 195: ...April 2021 Service and Repair Manual 183 Electrical Schematic Deutz TD 2 2 L3 Models ...
Page 198: ...Service and Repair Manual April 2021 186 Electrical Schematic Deutz TD 2 2 L3 Engine Harness ...
Page 199: ...April 2021 Service and Repair Manual 187 Electrical Schematic Deutz D 2 9 L4 Models ...
Page 203: ...April 2021 Service and Repair Manual 191 Electrical Schematic Perkins 404F E22T Models ...
Page 206: ...Service and Repair Manual April 2021 194 Electrical Schematic Perkins 404D 22 Models ...
Page 207: ...April 2021 Service and Repair Manual 195 Electrical Schematic Ford MSG 425 EFI Models ...
Page 210: ...Service and Repair Manual April 2021 198 Electrical Schematic Generators ...
Page 217: ......