Figure 30: Three VFD cutout display panel
assembly
Figure 31: Seven VFD cutout display panel
assembly
Reset switch
When the unit is equipped with a convenience
outlet, a reset switch is installed on the inner
wall of the low side control cabinet (see Figure
30 and Figure 31). The reset switch is provided as
a safeguard in case of an overload on the circuit
or a short circuit in the appliance plugged into
the circuit. If this switch trips frequently, the user
is advised to evaluate the appliance wiring or
amperage draw. The convenience outlet load should
not exceed 15 amps.
Unit enable switch
The unit enable switch is provided as a standard
feature below the display panel to disable the unit in
case of emergency or when the user needs to shut
down the unit instantly. The unit cannot be turned
ON unless this switch has been enabled. The display
remains ON when the unit enable switch is turned
OFF.
See Figure 26 and Figure 27 for location.
Tempmaster
®
Omni™ Premier 25 Ton to 80 Ton Rooftop Units Installation and Maintenance Guide
74
Tempmaster