4. Heat and discharge through heat option is used unless any of the following are included:
•
Discharge filters
•
Humidifier, sound attenuator, or blank post-evaporator section
•
Top or right discharge
•
Discharge plenum
5. Small post-evaporator blank can contain
blank
or
final filter
or
humidifier
or
sound attenuator
.
6. Large post-evaporator blank can contain
blank
or
sound attenuator and final filter
or sound
attenuator and humidifier
or
humidifier
or
sound attenuator
.
7. Discharge plenum is required with all units that are cooling only. Discharge plenum is required on all units with heat section cabinet.
8. Supply fan weights include the supply fan, motor, isolators, inlet guards, shaft grounding ring, variable frequency drive (VFD), line reactor, disconnect, and VFD bypass. On 60 ton
to 80 ton units, supply fan weights are for both fans and motors.
9. Economizer with belt driven exhaust/return fan includes the weight of the fan, isolator, shaft grounding rings, extended lube lines, and inlet guards.
10. For belt driven exhaust/return fan motor includes the weight of the motor, VFD, line reactor, and VFD bypass. For direct driven return fan, weight includes return fan and motor,
isolators, inlet guards, shaft grounding ring, VFD, line reactor. Return fan redundant VFD weight included under miscellaneous options.
11. All sizes of electric heat.
12. A transformer is required if convenience outlet, gas heat, lights, or high end display are selected.
13. Roof curb weight is not included with this table.
14. Considering standard cooling unit configuration the Refrigeration system weight includes condenser fan, compressor, piping, condenser coil, refrigerant, wire guards, condenser
sheetmetal and evaporator coil.
15. For units that are shipped split please contact your local sales office or use Selection Navigator to get the individual air handler and condenser unit weights.
16. For cooling only units with no post-evaporator blank, a 55 in. supply fan section length is available. All other units have a 74 in. supply fan section.
Dimensions
Figure 11: Rooftop unit component locations
Tempmaster
®
Omni™ Premier 25 Ton to 80 Ton Rooftop Units Installation and Maintenance Guide