56051701
–
Rev A
16
© 2019 Telguard
DC Terminal Strip Pin Assignments
Terminal Strip
Pin
Connects To
Function
Note
PANEL POWER
Panel auxiliary output
Power in to the Telguard
system
Regulated DC input power of 12VDC or
24VDC
POWER PASS
THRU
Second TG-PEM
Power out to second TG-
PEM
DC power to additional TG-PEM devices
TELGUARD
POWER
Telguard TG-7FS
Power out to the Telguard
DC power to the TG-7FS device
UL Note:
: For all UL listed installations, the panel needs to be listed for the application and the panel shall provide a regulated
12VDC or 24VDC from its output.
Wire Lengths
Gauge
Length of Wire Loop
Note
22
2000ft
1000ft in distance
18
5000ft
2500ft in distance
End of Line Resistors
Each supervised zone input must be terminated with a 2.2k
Ω