background image

56051701 

 Rev A 

 

9

 

© 2019 Telguard 

In some installations, it may be desirable or necessary to activate the TG-7 series communicator without 
utilizing the alarm panel.  If the TG-7 or TG-7FS meets the firmware requirement (minimum verson 2.32.00), 
the TG-PEM can be used to activate the communicator.  To initiate the activation process, perform the 
following steps.  

 

 

Make sure TG-7 or TG-7FS LEDs display normal operation (no RSSI mode). 

 

Short input zone 8. 

 

Press and release the RSSI toggle button to enter RSSI mode. 

 

Remove the short on input 8. 

 

Press and release the RSSI toggle button for a second time to exit RSSI mode. 

 

Observe the activating LED pattern on the TG-PEM.  TG-PEM LED D2 will flash amber while activating the 
TG-7 or TG-7FS.  

 

Look for the TG-7 series LED 1 to eventually turn solid green indicating it is activated. 

 

Configuration Changes 

To change the Configuration after activation, press and Hold the RSSI Button for more than 5 seconds and 
release.  This will put the TG-PEM and the communicator into a 10-minute maintenance mode window to 
accept the configuration commands from the Telguard Communications Center (for UL864, cl. 59.1.8 
reference purposes, TMC gateway software ver. 2019.1.16.2 or later is used).  You can only change the input 
configuration during the maintenance mode window.  

 

Step 7: Connect Zone Inputs (if using) 

The TG-PEM provides 8 dry contact zones.  Up to 16 zones are available by using a second TG-PEM.  There are 
restrictions that impact the use of zones in NFPA 72 that must be honored to remain in UL and/or ULC 
compliance for fire systems.  For example, initiating devices must be connected to the FACP, not the TG-PEM.  
Check with your AHJ to understand how these restrictions impact your installation. 

 

Prior to making connections to the zone inputs, verify that LED D2 on the TG-PEM is solid green.  If it is 
solid amber, your TG-PEM is not configured to use zone inputs and should be reconfigured.  Consult 
Appendix 3 for troubleshooting on any other light pattern appears. 

 

Temporarily disconnect the power while you connect any monitoring sensors to the zone inputs. 

 

For supervised zones, use a standard 2.2k

 EOL resistor (not included). 

 

Reconnect power, allow the TG-7 or TG-7FS to initialize, and check for proper operation. 

The red LED D1 is intended to assist with zone programming.  A captured event, such as a tripped zone, will turn the LED 
solid red, then begin flashing during the data exchange with the Telguard Messaging Center.  When event reporting is 
complete, LED D1 will return to previous state.  Individually check for proper operation of each programmed zone by 
causing it to trip, observe the LED, and verify the proper event code is reported. 

 

Check Proper Operation of Zones 

The red LED D1 is intended to assist with zone programming.  A captured event, such as a tripped zone, will turn the red 
LED solid, then begin flashing during the data exchange with the TCC.  When event reporting is complete, the LED D1 will 
return to previous state.  Individually check for proper operation of each programmed zone by causing it to trip, observe 
the LED, and verify the proper event code is reported.     

 

Summary of Contents for TG-PEM

Page 1: ...COMPANY CONFIDENTIAL For use by TELGUARD customers only Distribution to other parties strictly prohibited September 20 2019 Telguard TG PEM Power Expansion Module Installation Manual ...

Page 2: ...s measuring voltages stripping wire properly connecting wires together connecting wires to terminals and checking phone lines It also assumes that you have a familiarity with the proper installation and programming tasks related to various alarm panels The material and instructions covered in this manual have been carefully checked for accuracy and are presumed to be reliable However Telguard assu...

Page 3: ...supply is off for any reason however briefly The cellular radio network needed to transmit alarm signals from protected premises to a central monitoring station may be inoperable or temporarily out of service Cellular radio networks are also subject to compromise by sophisticated methods of attack This equipment like any other electrical device is subject to component failure Although this equipme...

Page 4: ...T IN AN ENVIRONMENT NOT PROVIDED OR PERMITTED BY TELGUARD IN WRITING THE PARTIES SHALL GIVE EACH OTHER PROMPT NOTICE OF ANY SUCH COST OR CLAIMS AND COOPERATE EACH WITH THE OTHER TO EFFECTUATE THIS INDEMNIFICATION DEFENSE AND HOLD HARMLESS WARRANTY and LIMITATIONS TELGUARD WILL REPAIR OR REPLACE OUR OPTION INOPERATIVE UNITS FOR UP TO TWO YEARS FROM DATE OF MANUFACTURE EXCLUDES DAMAGE DUE TO LIGHTNI...

Page 5: ...llation Checklist 5 Installation 6 Summary 6 Step 1 Register the TG 7 or TG 7FS Communicator 6 Step 2 Pre configure the TG PEM prior to installation 6 Step 3 Mount the TG 7 or TG 7FS Communicator 6 Step 4 Mount the TG PEM 7 Step 5 Connect the TG PEM to the TG 7 or TG 7FS Host 8 Step 6 Power Up and Configure 8 Step 7 Connect Zone Inputs if using 9 Check Proper Operation of Zones 9 Optional Connect ...

Page 6: ...e TG PEM System 13 Two TG PEM System 13 Wiring Diagrams 14 Main Terminal Strip Pin Assignments 15 DC Terminal Strip Pin Assignments 16 Wire Lengths 16 End of Line Resistors 16 Appendix 3 Troubleshooting Guide 17 LED Indicator Guide 17 Appendix 4 Power Specifications 18 Power consumption 18 ...

Page 7: ...or and a second TG PEM if equipped Powering from the panel eliminates the need for the communicator s external power supply and the backup battery within the metal enclosure The TG PEM has 8 dry contact inputs that may be configured as normally open normally closed or supervised zone Each zone can be configured independently as needed for your application Note The TG PEM is an accessory for a TG 7...

Page 8: ...edicated AC outlet and backup communicator battery at the protected premises Wire the panel auxiliary power to the TG PEM for the system to operate normally UL Note For all UL Listed installations the input must to be power limited by a panel that is UL Listed for compatible listing and provides a regulated output of either 12VDC or 24VDC Refer to Appendix 4 for load calculations Note When using p...

Page 9: ...cluding wiring faults when the inputs are in Supervised Mode STC2 relay NC shall be programmed to report NSC LFC RFC DTF UL Note Each input on any PEM module should have a unique zone number programmed Zone numbers can t be duplicated between two PEM modules Swinger Swinger is the repetitive opening and closing of a detection circuit or device for no apparent reason Some central stations may refer...

Page 10: ...red from www telguard com Note The STC1 relay is limited to tripped or restored condition The STC1 relay is energized in a powered up state when no system troubles exist For more information refer to the TG 7 Series Installation and Operating Guide UL Note for Commercial Fire applications STC1 shall be configured for Trouble Condition on the TG PEM and all trouble conditions from the TG 7FS Progra...

Page 11: ...n to the FACP you will need to call Telguard Technical Support 1 800 229 2326 option 9 for assistance Pre Installation Checklist Before attempting to install the TG PEM in to the Telguard enclosure please make sure you have all the proper parts at the job site The following items are shipped with each TG PEM Telguard TG PEM Mounting bracket Three mounting screws Data cable Quick Install Guide You ...

Page 12: ...lling a Telguard TG PEM Please follow the instructions carefully and if you should need assistance or have any questions please call Telguard Technical Support at 1 800 229 2326 extension 9 Note Complete Dealer Account Establishment and Telguard Registration prior to Installation Step 1 Register the TG 7 or TG 7FS Communicator Use the dealer portal at www telguard com Do not actually mount or inst...

Page 13: ...emove top left mounting screw that holds the TG 7 series board indicated by arrow Orient bracket as shown in diagram Insert bracket at an angle so that top mounting point slides under board as depicted and angled tab threads through the enclosure bump out Replace screw to securely mount bracket and board Use the three provided mounting screws to secure the TG PEM board onto the bracket in the hole...

Page 14: ...Guide The TG PEM does not require a separate activation but will require an active TG 7 or TG 7FS host If the TG PEM was preconfigured it should now be ready otherwise visit www telguard com to configure the TG PEM When both the TG 7 series communicator and the TG PEM have been activated LED D2 on the TG PEM should have a solid light on If the TG PEM was configured to be used as a power supply onl...

Page 15: ...pact the use of zones in NFPA 72 that must be honored to remain in UL and or ULC compliance for fire systems For example initiating devices must be connected to the FACP not the TG PEM Check with your AHJ to understand how these restrictions impact your installation Prior to making connections to the zone inputs verify that LED D2 on the TG PEM is solid green If it is solid amber your TG PEM is no...

Page 16: ...C1 relay must be connected to the panel s input zone to annunciate trouble condition in TG PEM and TG 7FS For commercial burglary applications any inputs from TG PEM may be configured to trip the STC1 relay on the TG 7 to annunciate the alarm or trouble condition locally on the alarm panel using a 24 hour input on the panel Complete the Telguard Power and Expansion Module Installation Route and se...

Page 17: ...a second TG PEM use one of the screws provided to pre thread the screw holes in the metal mounting bracket While not required this will make attaching the TG PEM circuit board to the metal bracket much easier Make sure to pre thread the holes that will be on the left when the bracket is installed as shown below Remove the bottom left mounting screw that holds the TG 7 series circuit board Orient t...

Page 18: ...tructions to connect first TG PEM Connect power and ground from POWER PASS THRU terminal of the first TG PEM to the PANEL POWER terminal on the second TG PEM Data Connections Follow instructions to connect first TG PEM Connect the provided ribbon cable from the keyed connector on the second TG PEM labeled TO HOST to the keyed connector on the first TG PEM labeled TO TG PEM See Appendix 2 for wirin...

Page 19: ...6 LED7 LED8 Alarm Panel Do Not Use these power connectors when using TG PEM Power from TG PEM TG PEM Panel Power DC DC STC2 STC1 TRIP BATT AC TG PEM TG 7FS LTE LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 Alarm Panel Burglary Systems STC1 needs to be connected to a 24 hour panel input zone to indicate alarm conditions from TG PEM STC2 could be used to indicate TG 7 trouble conditions Do Not Use these p...

Page 20: ...em The TG PEM device that is getting the panel power is referred to as the First TG PEM The second TG PEM device is optional and its connections are depicted in red T R SIM 1 2 3 4 5 Power LED LED Mode Toggle Button System Status LEDs TELGUARD TG 7 STC2 N C STC1 N O 1 2 3 5 6 1 2 1 2 1 3 2 4 Alarm Panel UL Note 1 Panel Power Te lguar d powe r Panel powe r Power pass thr u To TG PEM To Host Te lgua...

Page 21: ...ower Power pass thru To TG PEM To Host FACP UL Note 2 UL Note 2 STC1 needs to be connected to a panel input zone to indicate all trouble conditions Main Terminal Strip Pin Assignments Terminal Strip Pin Definition Connects To Function 1 Input 1 Monitoring device Input COM Common or ground Common ground Common ground 2 Input 2 Monitoring device Input 3 Input 3 Monitoring device Input COM Common or ...

Page 22: ...wer to additional TG PEM devices TELGUARD POWER Telguard TG 7FS Power out to the Telguard DC power to the TG 7FS device UL Note For all UL listed installations the panel needs to be listed for the application and the panel shall provide a regulated 12VDC or 24VDC from its output Wire Lengths Gauge Length of Wire Loop Note 22 2000ft 1000ft in distance 18 5000ft 2500ft in distance End of Line Resist...

Page 23: ...Input tripped or Event waiting to report on green At least 1 enabled input is tripped or Event s captured and waiting to be reported Event is reporting flashing green Event s reporting or waiting for response LED Test on amber Application is starting all LEDs on for 3sec followed by off for 3sec Firmware update off amber fast flash Updating TG PEM firmware Bootloader error off red flash Device fai...

Page 24: ... Specifications This section provides a power consumption summary for two 2 TG PEMs and TG 7FS combined Power consumption DC input mA standby no link supervision mA standby with link supervision mA transmit max 12V 78mA 82mA 278mA 24V 43mA 46mA 132mA ...

Reviews: