Commercial Fire Installation
The TG-7FS and the TG-PEM work together as a system. For commercial fire installations, one or two TG-PEM devices may
be used. FACP relay outputs are connected to TG-PEM zone inputs and the TG-7FS STC1 relay output is connected to a
FACP input zone to indicate all trouble conditions.
.
T
R
SIM
1
2
3
4
5
Power LED
LED Mode
Toggle Button
System Status
LEDs
TELGUARD
TG-7FS
STC2
(N.C.)
STC1
(N.O.)
1 2 3
5 6
1 2
1 2
1
3
2
4
TG-PEM
Telg uard
po wer
Pan el
po wer
Pow er
pa ss
thru
To
TG-PEM
To Host
FACP
UL Note 2
UL Note 2:
STC1 needs to be connected to a panel input zone to indicate all trouble conditions.
Main Terminal Strip Pin Assignments
Terminal
Strip Pin
Definition
Connects To
Function
1
Input 1
Monitoring device
Input
COM
Common (or ground)
Common/ground
Common/ground
2
Input 2
Monitoring device
Input
3
Input 3
Monitoring device
Input
COM
Common (or ground)
Common/ground
Common/ground
4
Input 4
Monitoring device
Input
5
Input 5
Monitoring device
Input
COM
Common (or ground)
Common/ground
Common/ground
6
Input 6
Monitoring device
Input
7
Input 7
Monitoring device
Input
COM
Common (or ground)
Common/ground
Common/ground
8
Input 8
Monitoring device
Input