TG-7 Dual Path Series Installation & Operating Guide
28
56052601 Rev B © 2022 Telguard
RJ-45 Jack Pin Assignments
Jack
Connects To
Pin Assignment
Function
Status LED Reference
Black
Digital Dialer
input/output
of host alarm
panel (DACT).
1 = Brown R1
2 = Blue
4 = Green R (Ring)
5 = Red T (Tip)
7 = Orange
8 = Gray T1
Connects alarm
panel to
communicator
for transmitting
alarm signals to
TCC.
If PPF is ENABLED,
STC LED 2 will flash 7
times when alarm panel
is not detected.
Silver
Router, Switch,
or other LAN
port.
Per CAT-5 or
higher standard.
Crossover cables
and PoE not
supported.
Connect
communicator
to premises LAN
for transmitting
alarm signals to
TCC via Internet.
LED 6 stays illuminated
for verified connection.
Otherwise, STC LED 2
will flash 3 times and
flash pattern on LED 6
will indicate reason.
DC Terminal Strip Pin Assignments
Terminal
Strip Pin
Definition
Connects To
Function
LED Reference
Note
1 GND
2 DC
Power
input
12- or 24-VDC
Regulated
Source
Provides
power to
the unit
Power LED 8 on
for valid power
Consumption rates vary
based on input voltage
used
Main Terminal Strip Pin Assignments
Terminal
Strip Pin
Definition
Connects To
Function
Status LED
Reference
1 STC2
2 STC2
Supervisory Relay
Trip output for
programmable
trouble conditions.
Normally Closed.
24-hour trip
zone input
on alarm
panel.
Enables transmission of
programmed supervisory
trouble code (see diagram
or installation section).
STC LED 2
3 STC1
4 STC1
Supervisory Relay
Trip output for
programmable
trouble conditions.
Normally Open.
24-hour trip
zone input
on alarm
panel.
Enables transmission of
programmed supervisory
trouble code (see diagram
or installation section).
STC LED 2
5 GND
6 IN
Trip Ground and
Trip Input
External trip
relay.
Allows an external relay to
trigger an alarm signal.
LED 7