MX 16
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
52
NP16EN
Revision: A.0
•
Highest alarm set point for flammable gases shall not exceed 60% LEL and shall be of
a latching type.
•
Over-range (flammable gases)
As soon as gas concentration exceeds 100% LEL,
MX 16 stores the over-range
condition and displays
>100% LEL. The concerned channel goes into alarm and fault
condition and OVS
(OVERSCALE) and FAULT (FAULT) visual indicators are lit.
Alarm reset is manual and under the responsability of the user who must follow the
site-specific safety guidelines. Over-range condition can only be deactivated by
switching off the detector via the maintenance menu providing the gas concentration
is below the alarm threshold.
MX 16
controller must not be exposed to mechanical vibrations and must be installed in a
non-hazardous area.
With respect to installation in explosive atmospheres, the electrical installation must
comply with the regulation in force, in particular EN 60079-14 and EN 6079-17 standards
(current editions) and, if necessary, additional requirements of domestic or national
regulations that apply to the place of installation.
Summary of Contents for Oldham MX 16
Page 1: ...NP16EN Revision A 0 MX 16 ANALOG AND DIGITAL CONTROLLER Version Easy Duo USER GUIDE...
Page 8: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 4 NP16EN Revision A 0...
Page 22: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 18 NP16EN Revision A 0...
Page 38: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 34 NP16EN Revision A 0...
Page 42: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 38 NP16EN Revision A 0...
Page 44: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 40 NP16EN Revision A 0...
Page 58: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 54 NP16EN Revision A 0...
Page 59: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE NP16EN Revision A 0 55...