Connecting detectors other than TELEDYNE OLDHAM
SIMTRONICS detectors to the MX 16 controller
Any user wishing to use detectors other than TELEDYNE OLDHAM SIMTRONICS detectors must
ensure that they are compatible with the controller, in order the complete installation to be
considered as a safety device.
Transfer table
The following table shows the controller status depending on the detector analog signal output.
In the event the user connects a non- TELEDYNE OLDHAM SIMTRONICS brand detector to the
MX 16 controller, the user must ensure that the detector is compatible with the input characteristics
of the controller, so that the information delivered by the detector will be properly interpreted. In
addition, the controller must provide sufficient supply voltage, taking into account voltage drops
in the cable.
Detector signal
ouput
MX 16 Status
0 to 2.4 mA
Fault
>2.4 to 21.6mA
Measurement
>21.6 mA
Over Range Fault
Summary of Contents for Oldham MX 16
Page 1: ...NP16EN Revision A 0 MX 16 ANALOG AND DIGITAL CONTROLLER Version Easy Duo USER GUIDE...
Page 8: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 4 NP16EN Revision A 0...
Page 22: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 18 NP16EN Revision A 0...
Page 38: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 34 NP16EN Revision A 0...
Page 42: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 38 NP16EN Revision A 0...
Page 44: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 40 NP16EN Revision A 0...
Page 58: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 54 NP16EN Revision A 0...
Page 59: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE NP16EN Revision A 0 55...