Alarm Reset
is pressed
AL(1,2)
grayscale mode
Activated if event
is still present
Solid if event is
still present
OFF
AL(1,2,3)
grayscale mode
Deactivated if the
event has
disappeared
OFF if the event
has disappeared
OFF
Alarm
Disappearance
Normal mode
(a)
Deactivated
(a)
OFF
(a)
OFF
(a)
(a): Once Alarm Reset button has been pressed
Table 1: Alarms in Manual Acknowledgement mode
Alarms Automatic Acknowledgement
In this mode, resetting an alarm does not require any intervention. Alarm management (relays,
visual indicators, buzzer) is as follows:
This mode is not a Standard mode (Consult us)
Event
Display
Alarm
Relay
(normal mode)
Alarm LED
Internal buzzer
Alarm
Appearance
AL (1,2)
grayscale mode
Activated
Solid
ON
Alarm Reset
is pressed
AL (1,2)
grayscale mode
Activated
Solid
OFF
Alarm
Disappearance
Normal mode
Deactivated
(a)
OFF
(b)
(a): Automatic deactivation upon alarm disappearance even if Alarm Reset button was not pressed
(b): Manual acknowledgement (press Alarm Reset) is mandatory to silence the internal buzzer
Table 2: Alarms in Automatic Acknowledgement mode
Summary of Contents for Oldham MX 16
Page 1: ...NP16EN Revision A 0 MX 16 ANALOG AND DIGITAL CONTROLLER Version Easy Duo USER GUIDE...
Page 8: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 4 NP16EN Revision A 0...
Page 22: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 18 NP16EN Revision A 0...
Page 38: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 34 NP16EN Revision A 0...
Page 42: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 38 NP16EN Revision A 0...
Page 44: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 40 NP16EN Revision A 0...
Page 58: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 54 NP16EN Revision A 0...
Page 59: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE NP16EN Revision A 0 55...