MX 16
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
48
NP16EN
Revision: A.0
Address SENSORS
[64 + 2]
Nb
bytes
Data type
1 Com sensor
2 X 16 Unicode text (16 bits) 16
characters including the final
/0.
17 Status
2
Start / Stop: if in operation,
variable = 1. If stopped,
variable = 0.
18 Gas name
2 x 20 Unicode text (16 bits) 20
characters including the final
/0.
38 Range
2
Value The range is from 1 to
5000.
Range X 10 display format.
The display format is given in
another box.
39 Display format 2
Coded value.
40 Unit
2 X 5
Unicode text (16 bits) 5
characters including the final
/0.
45 Abbreviated
gas name
2 x 6
Unicode text (16 bits) 6
characters including the final
/0.
CAUTION, if the first 2 letters
= O2: special treatment.
51 Zone
2
Value
1 to 8
52 Instantaneous
alarm
threshold 1
2
Value
-999 to 9999 (real value to be
multiplied like the range)
53 Instantaneous
alarm
threshold 2
2
Value
-999 to 9999 (real value to be
multiplied like the range)
54 Instantaneous
alarm
threshold 3
2
Value
-999 to 9999 (real value to be
multiplied like the range)
55 Average alarm
threshold 1
2
Value
-999 to 9999 (real value to be
multiplied like the range)
56 Average alarm
threshold 2
2
Value
-999 to 9999 (real value to be
multiplied like the range)
57 Average alarm
threshold 3
2
Value
-999 to 9999 (real value to be
multiplied like the range)
58 Underscale
threshold
2
Value
-999 to 9999 (real value to be
multiplied like the range)
59 Overscale
threshold
2
Value
-999 to 9999 (real value to be
multiplied like the range)
60 Default low
threshold
2
Value
-999 to 9999 (real value to be
multiplied like the range)
61 Out of range
threshold
2
Value
-999 to 9999 (real value to be
multiplied like the range)
62 Integration
time alarm 1
2
Value
15 - 480 min per 1min step (if not
used, put 15 min)
63 Integration
time alarm 2
2
Value..
15 - 480 min per 1min step (if not
used, put 15 min)
64 Integration
time alarm 3
2
Value
15 - 480 min per 1min step (if not
used, put 15 min)
65 Hysteresis
2
Value
Caution, max = 5% of the range.
Always use a positive value and
not a percentage.
66 Alarm active?
2
Configuration per bit
Al active inst, avg: 1, 2, 3.
bit6
bit5
bit4
bit3
bit2
bit1
bit0
Summary of Contents for Oldham MX 16
Page 1: ...NP16EN Revision A 0 MX 16 ANALOG AND DIGITAL CONTROLLER Version Easy Duo USER GUIDE...
Page 8: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 4 NP16EN Revision A 0...
Page 22: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 18 NP16EN Revision A 0...
Page 38: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 34 NP16EN Revision A 0...
Page 42: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 38 NP16EN Revision A 0...
Page 44: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 40 NP16EN Revision A 0...
Page 58: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE 54 NP16EN Revision A 0...
Page 59: ...MX 16 ANALOG AND DIGITAL CONTROLLER USER GUIDE NP16EN Revision A 0 55...