background image

8

 type 258

Do not apply 

power here!

Maximum 24 Volts

10A

Safety Divider

24

Vac

120

or

240
Vac

External 24Vac 

60Hz class II 

transformer

System Pump 

Relay

closes to turn on 

System Pump 

10K Zone 

Control 

(optional)

Unoccupied 

Switch (optional)  

to switch control to 

Unoccupied mode

Outdoor 

Sensor

070

Supply

Sensor

 071

26

27

28

29

30

UnO 

Sw

Com 

Sen

10K 

Zone

Sup 

Sen

Out 

Sen

6

7

8

5

1

2

3

4

Dem

10A

9

10

10A

11

12

10A

13

14

10A

15

16

Safety Divider

Stage

1

2

3

4

Stage

Stage

Stage

2

1

3

4

Dem

10A

17

18

10A

19

20

10A

21

22

8A

23

24

Stage

5

6

7

8

Stage

Stage

N/C

6

5

7

8

C

R

Power

Pmp Pmp

System

Comb.

air

25

8

Com N/O

Boiler Relays

close to turn on boilers

10A

Combustion

air Relay

closes to operate

Combustion air damper 

Heat Demand

Apply a 24Vac signal 

to request heat

to the system

Heat

Connect the stage 1 boiler circuit to terminals 

Stage 1 (9

and 10). These terminals lead to a 10 amp dry relay
contact which closes when the control requires boiler
operation. Repeat this step with the correct  terminals for
each additional stage. Boilers with 24Vac control circuits
can be switched directly through the control. If higher
voltages are used, isolation relays must be added.

8

9

10

11

12

13

14

15

16

Stage

1

2

3

4

Stage

Stage

Stage

2

1

3

4

17

18

19

20

21

22

23

24

Stage

5

6

7

8

Stage

Stage

N/C

6

5

7

8

b.

r

25

8

Com N/O

Powered input connections

If a 24Vac external 

Heat Demand signal is used, (zone valve end switches, etc.) connect

the wiring from the Heat Demand circuit to terminals 

Heat Dem (5 and 6). When 24Vac

is applied to these terminals, the control will recognize a "call for heat" from the system.
DIP switch must be set to "Reset"

If a 24Vac 

Setpoint Demand signal is used, (aquastat, etc.) connect the wiring from the

Setpoint Demand circuit to terminals 

Heat Dem (5 and 6). When 24Vac is applied to these

terminals, the control will recognize a "call for Setpoint temperature" and switch into
Setpoint mode.  

DIP switch must be set to "Stpnt"

6

7

8

5

Dem

9

10

11

12

13

Stage

1

2

3

Stage

2

1

Dem

Comb.

air

Heat

Sensor and unpowered input connections

Power should never be applied to these terminals.

Damage to the control will result.

Connect the two wires from the Outdoor Sensor 070 to terminals
Com Sen — Out Sen  (28 and 30).

Connect the two wires from the Supply Sensor 071 to terminals
Com Sen — Sup Sen  (28 and 29).

Do not apply power here!

26

27

28

29

30

UnO 

Sw

Com 

Sen

10K 

Zone

Sup 

Sen

Out 

Sen

26

27

28

29

30

UnO 

Sw

Com 

Sen

10K 

Zone

Sup 

Sen

Out 

Sen

Option:  Indoor temperature feedback, tekmar 10K Zone Control Only

Connect the two wires from a tekmar 10K Zone Control to terminals
10K Zone  — Com Sen (27 and 28).

Option:  Occupied/Unoccupied switch input, when not using Internal timer

Connect the two wires from the Occupied/Unoccupied dry contact switch
(timer, relay, etc.) to terminals 

UnO Sen — Com Sen  (26 and 28).

26

27

28

29

30

UnO 

Sw

Com 

Sen

10K 

Zone

Sup 

Sen

Out 

Sen

26

27

28

29

30

UnO 

Sw

Com 

Sen

10K 

Zone

Sup 

Sen

Out 

Sen

Electrical connections to the terminal plugs of the 258 control. Control relays are shown in "power down" condition.

Note: This is not a Wiring Diagram. 

For a detailed wiring schematic of

your specific application, refer to the Application Brochure A 258.

Summary of Contents for Eight Stage Boiler Control 258

Page 1: ...mand Minimum WWSD Pump Stage 1 Stage 2 Comb air Stage 3 Stage 6 Stage 5 Stage 8 Stage 7 Stage 4 Menu Item Override Setpoint Actual Supply Target Supply S PRGM TEMP F C TIME USE AMPM UNOCC OVR M T W T...

Page 2: ...ugh water to keep the room temperature warm particularly during the colder weather If the Heating Curve selected is too high the supply water will be too hot for the conditions and the building will o...

Page 3: ...ntrol The effect of the Integral function can also be easily viewed by not allowing a rise in supply temperature when the control asks for more heat The displayed target temperature will show a slow b...

Page 4: ...allow Heating Curve operation System pump light on the system pump relay is on closing the contacts between terminals System Pmp 3 4 Comb air light on the combustion air relay is on closing the contac...

Page 5: ...e Occupied room temperature setting the control enters WWSD When switched into Unoccupied mode the UNOCC display element will replace the OCC display element and the control will switch from operating...

Page 6: ...e Stage and Comb air lights will be shut off with the boilers and combustion air damper The control will continue to cycle the boilers and combustion air damper to maintain the supply at the target te...

Page 7: ...lighter guage wire is too fragile and may also contribute too much resistance to the circuit Power should not be applied to any of the wires during this rough in wiring stage Step Four Electrical con...

Page 8: ...nals Heat Dem 5 and 6 When 24Vac is applied to these terminals the control will recognize a call for heat from the system DIP switch must be set to Reset If a 24Vac Setpoint Demand signal is used aqua...

Page 9: ...powered up the combustion air damper should operate If it does not come on check the circuit wiring for errors and ensure that it is powered up and the voltage is correct Check the devices in the cir...

Page 10: ...e Heating Curve use the following formula Outdoor air temperature Supply water temperature 50 10 30 1 10 12 10 F 23 C 110 43 70 21 70 21 90 32 210 99 170 77 150 65 130 54 190 88 3 6 3 0 2 4 2 0 1 6 0...

Page 11: ...w Domestic Hot Water boilers to be switched over to assist the heating boilers during peak load times Int timer switch The 258 control has an internal timer programmed using the LCD display and keypad...

Page 12: ...tback and delivering cold water to the boilers increased load Typically this will cause many or all of the boilers to be staged on with minimum delay which is the correct control action for the situat...

Page 13: ...ustion air damper will remain open After the 5 minutes the control will automatically exit the test routine and enter the normal operating mode If there is no Heat Demand the control will not allow a...

Page 14: ...ply temperatures and the LED system status lights display the operation of the various system components A competent troubleshooter can locate system faults without having to go any further than obser...

Page 15: ...tual Supply Target Supply F S TEMP OCC S M W T F T Auto Stage 1 2 3 4 5 6 7 8 Perm Demand Ext timer Fixed last Int timer Lo Hi fire Fixed lead Rotate Off 1 2 3 4 5 6 7 8 9 External Demand Off 1 2 3 4...

Page 16: ...ress or to change the day pointer PROGRAM MENU VIEWING Must be set to Int timer Auto 1 2 3 4 5 6 7 8 Perm Demand Ext timer Int timer Off 1 2 3 4 5 6 7 8 9 External Demand Off 1 2 3 4 5 6 Stpnt Reset P...

Page 17: ...button when the control is showing a fixed display Setpoint Actual Supply Target Supply F S TEMP S M W T F T OVR UNOCC Which mode is selected See page 3 Menu Item Override Menu Item Override Menu Item...

Page 18: ...nOcc 1 5 00 pm Occ 2 10 30 pm UnOcc 2 Friday 6 00 am Occ 1 8 30 am UnOcc 1 5 00 pm Occ 2 11 30 pm UnOcc 2 Saturday 8 00 am Occ 1 11 30 pm UnOcc 1 Null Occ 2 Null UnOcc 2 Schedule P 5 Day Time Temperat...

Page 19: ...when powered down for up to 10 years Battery backup Maintains clock operation for 24hrs when powered down Dial Switch Settings Heating Curve 0 4 to 3 6 Minimum Off 80 to 170 F Off 27 to 77 C Boiler D...

Page 20: ...antability and fitness for a particular purpose shall not extend beyond 24 months from the date of invoice or 12 months from the date of installation of the product whichever occurs first Replacements...

Reviews: