background image

3

Notes on the operation of a PID control and the effect of the PID processing function on target temperature

calculations and control response to temperature change.

In order to reduce excessive temperature droop or overshoot

and more smoothly stage the boilers on and off, this control uses an
advanced Propor In Derivative processing algorithm
to calculate target temperatures. When a desired temperature
– such as a setpoint – is programmed into the control, the control will
initially use that setting as the exact target temperature. The PID
function however, can affect the calculation of the target tempera-
ture in two significant ways. As an example; when there is a 

rapid

increase in the actual temperature (Derivative), the control will
calculate a lower target temperature than the setpoint in order to
slow down or reverse the staging on of the boilers or; when the actual
temperature 

remains above the setpoint for a long period of time

without changing (Integral), the control will calculate a lower target
temperature in order to more quickly stage the boilers off. Any
change in the calculated target temperature will show up as a
temporary deviation in the LCD target temperature display. The
deviation in target temperature will be reduced as the actual tem-
perature approaches the desired temperature. This display function
can be a useful tool in troubleshooting system problems, and is
discussed in more detail in other sections of this brochure.

The effect of the derivative function can easily be viewed when

the "target temperature" fixed display is selected. Certain rapid

control adjustments will have a temporary effect on the target
temperature. By quickly turning up the Heating Curve dial for
instance, the operator will introduce enough derivative error to the
control to drive the target temperature artificially high for a few
seconds. This type of control response is no cause for alarm since
the displayed target temperature will automatically return to normal
when the dials are left alone for 20 seconds, as the control resets
itself. This type of reaction to a sudden change illustrates an
important point that should be considered when designing with PID
controls. 

Flow rate and system load changes should be made as

slowly as possible in order to prevent overreaction by the control.

The effect of the Integral function can also be easily viewed by

not allowing a rise in supply temperature when the control asks for
more heat. The displayed target temperature will show a slow but
steady increase, illustrating another important point. 

Whenever the

control asks for a change in temperature – ie. stages a boiler on or
off – the control sensor must be able to detect a change as soon as
possible or it will operate too many boilers. (Do not install sensors on
return lines). If a multiple boiler system has adequate, continuous
flow and slowly changing load conditions, the result will be very
smooth staging, minimal temperature droop or overshoot and oper-
ating characteristics that will provide stable temperature control.

The 258 Display

PRGM

F C

S

TEMP
T I M E

USE

ROOM

OUTSIDE

AMPM

UNOCC

OVR

S

M

W T F

T

1

2

On when any 

temperature 

is displayed

On when any 

time is displayed

On when displaying setback 

program selection or when 

programming setback 

schedule 

Alpha/numeric 

time/temperature 

display elements

On when the room 

temperature selection 

is displayed

On when the outdoor 
temperature is displayed

On when the control is 

operating on the #1 setback 

program event

On when the control is 

operating on the #2 setback 

program event

Slowly flashes on & off (temporary), 

or is on constantly (permanent), 

when override function is operating

Day of week 

marker on when 

time is displayed

On when any 

boiler running 

time is displayed

Either 

°

F or 

°

C marker 

on when temperature 
is displayed

Either AM or PM marker on 
when time is displayed

Either OCC or UNOCC 
marker on when time or 
temperature is displayed

The 258 "Fixed display" options.   All other displays will time-out to "ACTUAL SUPPLY – #1" 

after 20 seconds with no keypad action.    

See "Programming" Section, Pg. 15, for description 

Setpoint

Actual
Supply

Target
Supply

F

S

TEMP

OCC

S

M

W T F

T

ACTUAL SUPPLY – #1

F

S

TEMP

OCC

S

M

W T F

T

Setpoint

Actual
Supply

Target
Supply

TARGET SUPPLY – #2

S

T I M E

PM

UNOCC

S

M

W T F

T

1

TIME/DAY – #4

F

S

TEMP

OUTSIDE

OCC

S

M

W T F

T

OUTDOOR TEMP. – #3

Default fixed display.  When
first powered-up, or when
other displays are allowed to
"time-out", the control will
constantly display the supply
sensor temperature.

This fixed display shows the
supply temperature that has
been calculated by the
control to meet the require-
ments of the Heating Curve
or setpoint.

This fixed display shows the time
of day, day of week and some of
the current program operation
information.

This fixed display shows the
outdoor temperature sensor
reading.

Summary of Contents for Eight Stage Boiler Control 258

Page 1: ...mand Minimum WWSD Pump Stage 1 Stage 2 Comb air Stage 3 Stage 6 Stage 5 Stage 8 Stage 7 Stage 4 Menu Item Override Setpoint Actual Supply Target Supply S PRGM TEMP F C TIME USE AMPM UNOCC OVR M T W T...

Page 2: ...ugh water to keep the room temperature warm particularly during the colder weather If the Heating Curve selected is too high the supply water will be too hot for the conditions and the building will o...

Page 3: ...ntrol The effect of the Integral function can also be easily viewed by not allowing a rise in supply temperature when the control asks for more heat The displayed target temperature will show a slow b...

Page 4: ...allow Heating Curve operation System pump light on the system pump relay is on closing the contacts between terminals System Pmp 3 4 Comb air light on the combustion air relay is on closing the contac...

Page 5: ...e Occupied room temperature setting the control enters WWSD When switched into Unoccupied mode the UNOCC display element will replace the OCC display element and the control will switch from operating...

Page 6: ...e Stage and Comb air lights will be shut off with the boilers and combustion air damper The control will continue to cycle the boilers and combustion air damper to maintain the supply at the target te...

Page 7: ...lighter guage wire is too fragile and may also contribute too much resistance to the circuit Power should not be applied to any of the wires during this rough in wiring stage Step Four Electrical con...

Page 8: ...nals Heat Dem 5 and 6 When 24Vac is applied to these terminals the control will recognize a call for heat from the system DIP switch must be set to Reset If a 24Vac Setpoint Demand signal is used aqua...

Page 9: ...powered up the combustion air damper should operate If it does not come on check the circuit wiring for errors and ensure that it is powered up and the voltage is correct Check the devices in the cir...

Page 10: ...e Heating Curve use the following formula Outdoor air temperature Supply water temperature 50 10 30 1 10 12 10 F 23 C 110 43 70 21 70 21 90 32 210 99 170 77 150 65 130 54 190 88 3 6 3 0 2 4 2 0 1 6 0...

Page 11: ...w Domestic Hot Water boilers to be switched over to assist the heating boilers during peak load times Int timer switch The 258 control has an internal timer programmed using the LCD display and keypad...

Page 12: ...tback and delivering cold water to the boilers increased load Typically this will cause many or all of the boilers to be staged on with minimum delay which is the correct control action for the situat...

Page 13: ...ustion air damper will remain open After the 5 minutes the control will automatically exit the test routine and enter the normal operating mode If there is no Heat Demand the control will not allow a...

Page 14: ...ply temperatures and the LED system status lights display the operation of the various system components A competent troubleshooter can locate system faults without having to go any further than obser...

Page 15: ...tual Supply Target Supply F S TEMP OCC S M W T F T Auto Stage 1 2 3 4 5 6 7 8 Perm Demand Ext timer Fixed last Int timer Lo Hi fire Fixed lead Rotate Off 1 2 3 4 5 6 7 8 9 External Demand Off 1 2 3 4...

Page 16: ...ress or to change the day pointer PROGRAM MENU VIEWING Must be set to Int timer Auto 1 2 3 4 5 6 7 8 Perm Demand Ext timer Int timer Off 1 2 3 4 5 6 7 8 9 External Demand Off 1 2 3 4 5 6 Stpnt Reset P...

Page 17: ...button when the control is showing a fixed display Setpoint Actual Supply Target Supply F S TEMP S M W T F T OVR UNOCC Which mode is selected See page 3 Menu Item Override Menu Item Override Menu Item...

Page 18: ...nOcc 1 5 00 pm Occ 2 10 30 pm UnOcc 2 Friday 6 00 am Occ 1 8 30 am UnOcc 1 5 00 pm Occ 2 11 30 pm UnOcc 2 Saturday 8 00 am Occ 1 11 30 pm UnOcc 1 Null Occ 2 Null UnOcc 2 Schedule P 5 Day Time Temperat...

Page 19: ...when powered down for up to 10 years Battery backup Maintains clock operation for 24hrs when powered down Dial Switch Settings Heating Curve 0 4 to 3 6 Minimum Off 80 to 170 F Off 27 to 77 C Boiler D...

Page 20: ...antability and fitness for a particular purpose shall not extend beyond 24 months from the date of invoice or 12 months from the date of installation of the product whichever occurs first Replacements...

Reviews: