background image

Shifting the Heating Curve

(a) Manually, at the control:

The Occupied and Unoccupied room temperature settings of this control
can shift the WWSD point up or down from 35 to 105

°

F (2 to 41

°

C).

(b) Automatically, using room temperature feedback:

In addition to a Supply Sensor and an Outdoor Sensor, this control can use
a tekmar 10K Zone Control to provide room temperature feedback for
added comfort and system flexibility.

The control still calculates a desired supply temperature based on the
Heating Curve setting and the outdoor temperature.

If the air temperature in any one zone is too cold, the control will shift the
Heating Curve (and WWSD point) 

up, which raises the supply temperature

until the zone warms up again. The zone control will operate zone valves
or pumps in the warm zones to prevent overheating in those zones.

If the air temperature in all zones is too warm, the control will shift the
Heating Curve (and WWSD point) 

down, which lowers the supply tempera-

ture until the zones cool down.

Correct setting and shifting of the Heating Curve...  the key to More Comfort and Energy Savings.

Heating Curve

As outdoor temperatures become colder, heat losses from a building increase and require the addition of more heat in order to prevent
the indoor air temperature from becoming colder as a result. This tekmar reset control measures the outdoor temperature, and as
the outdoor temperature becomes colder the control will balance the heat loss by making the heating supply water hotter.
The Heating Curve is used to calculate exactly how hot to make the supply water at different outdoor temperatures, as it determines
the number of degrees the supply water temperature is raised for each degree the outdoor temperature falls.

Setting the Heating Curve

Two examples of how the Heating Curve works are illustrated in the following diagram.

—With a 2.4 Curve, the supply water temperature is raised 2.4 degrees for every degree of outdoor temperature drop.

If:  WWSD point = 70

°

F and Outdoor temperature = 30

°

F, then supply temperature = 166

°

F

—With a 0.6 Curve, the supply water temperature is raised 0.6 degrees for every degree of outdoor temperature drop.

If:  WWSD point = 70

°

F and Outdoor temperature = 30

°

F, then supply temperature = 94

°

F

2

• If the Heating Curve selected is too low;  the heating system will not

supply hot enough water to keep the room temperature warm,
particularly during the colder weather.

• If the Heating Curve selected is too high;  the supply water will be too

hot for the conditions and the building will overheat, particularly
during the colder weather.

Warm Weather Shut Down (WWSD)

At warm outdoor temperatures, the indoor space of a building gains heat
from the outdoors; additional heat is not required, and if the heating system
is running (even on standby), enough excess heat can be produced to
overheat the building, causing discomfort and wasting valuable energy.
This control shuts off the boilers and system pump when the outdoor
temperature is above the WWSD point.

As outdoor temperatures get colder, there comes a point where the heat
gain turns into heat loss; the heat loss causes the indoor temperature to fall
below the comfort level, and the heating system must be turned on.

Refer to the tekmar Essays E 001 and E 002 for more detailed information regarding control strategy and integration of control functions.

Outdoor Reset Strategy

A very cool zone temperature can shift the curve far enough up to bring the control out of WWSD at warm outdoor temperatures.
Very warm zone temperatures can shift the curve far enough down to put the control into WWSD at cool outdoor temperatures.

To provide heat to the building, this control opens the combustion air damper (if one is used), turns on the system pump and fires
the boilers to deliver heat at the low output required by the Heating Curve near the WWSD point. If the outdoor temperature rises above
the WWSD point, the control shuts the heating system off again, and since the system was operating at a low heat output level,
overheating and temperature swings in mild weather are avoided.

When the outdoor temperature is near the WWSD point and the building is too cold;  the WWSD point should be raised.
When the outdoor temperature is near the WWSD point and the building is too warm;  the WWSD point should be lowered.

Outdoor air  temperature

Supply water temperature

50

(10)

30

(-1)

10

(-12)

-10

°

F

(-23)

°

C

110

(43)

70

(21)

70

(21)

90

(32)

210

(99)

170 

(77)

150 

(65)

130 

(54)

190

(88)

3.6 3.0 2.4 2.0

1.6

0.8

0.4

1.0

0.6

90

(32)

50

°

F

(10)

°

C

Heating

Curve

WWSD

Point

1.2

Outdoor air  temperature

Supply water temperature

50

(10)

30

(-1)

10

(-12)

-10

°

F

(-23)

°

C

110

(43)

70

(21)

70

(21)

90

(32)

210

(99)

170 

(77)

150 

(65)

130 

(54)

190

(88)

3.6 3.0 2.4 2.0

1.6

0.8

0.4

1.0

90

(32)

50

°

F

(10)

°

C

Heating

Curve

WWSD

Point 

will 

shift 

up and 

down 

with 

shift of 

Heating 

Curve

1.2

UP

DOWN

UP

DOWN

Parallel Shift of Heating Curve

0.6

Summary of Contents for Eight Stage Boiler Control 258

Page 1: ...mand Minimum WWSD Pump Stage 1 Stage 2 Comb air Stage 3 Stage 6 Stage 5 Stage 8 Stage 7 Stage 4 Menu Item Override Setpoint Actual Supply Target Supply S PRGM TEMP F C TIME USE AMPM UNOCC OVR M T W T...

Page 2: ...ugh water to keep the room temperature warm particularly during the colder weather If the Heating Curve selected is too high the supply water will be too hot for the conditions and the building will o...

Page 3: ...ntrol The effect of the Integral function can also be easily viewed by not allowing a rise in supply temperature when the control asks for more heat The displayed target temperature will show a slow b...

Page 4: ...allow Heating Curve operation System pump light on the system pump relay is on closing the contacts between terminals System Pmp 3 4 Comb air light on the combustion air relay is on closing the contac...

Page 5: ...e Occupied room temperature setting the control enters WWSD When switched into Unoccupied mode the UNOCC display element will replace the OCC display element and the control will switch from operating...

Page 6: ...e Stage and Comb air lights will be shut off with the boilers and combustion air damper The control will continue to cycle the boilers and combustion air damper to maintain the supply at the target te...

Page 7: ...lighter guage wire is too fragile and may also contribute too much resistance to the circuit Power should not be applied to any of the wires during this rough in wiring stage Step Four Electrical con...

Page 8: ...nals Heat Dem 5 and 6 When 24Vac is applied to these terminals the control will recognize a call for heat from the system DIP switch must be set to Reset If a 24Vac Setpoint Demand signal is used aqua...

Page 9: ...powered up the combustion air damper should operate If it does not come on check the circuit wiring for errors and ensure that it is powered up and the voltage is correct Check the devices in the cir...

Page 10: ...e Heating Curve use the following formula Outdoor air temperature Supply water temperature 50 10 30 1 10 12 10 F 23 C 110 43 70 21 70 21 90 32 210 99 170 77 150 65 130 54 190 88 3 6 3 0 2 4 2 0 1 6 0...

Page 11: ...w Domestic Hot Water boilers to be switched over to assist the heating boilers during peak load times Int timer switch The 258 control has an internal timer programmed using the LCD display and keypad...

Page 12: ...tback and delivering cold water to the boilers increased load Typically this will cause many or all of the boilers to be staged on with minimum delay which is the correct control action for the situat...

Page 13: ...ustion air damper will remain open After the 5 minutes the control will automatically exit the test routine and enter the normal operating mode If there is no Heat Demand the control will not allow a...

Page 14: ...ply temperatures and the LED system status lights display the operation of the various system components A competent troubleshooter can locate system faults without having to go any further than obser...

Page 15: ...tual Supply Target Supply F S TEMP OCC S M W T F T Auto Stage 1 2 3 4 5 6 7 8 Perm Demand Ext timer Fixed last Int timer Lo Hi fire Fixed lead Rotate Off 1 2 3 4 5 6 7 8 9 External Demand Off 1 2 3 4...

Page 16: ...ress or to change the day pointer PROGRAM MENU VIEWING Must be set to Int timer Auto 1 2 3 4 5 6 7 8 Perm Demand Ext timer Int timer Off 1 2 3 4 5 6 7 8 9 External Demand Off 1 2 3 4 5 6 Stpnt Reset P...

Page 17: ...button when the control is showing a fixed display Setpoint Actual Supply Target Supply F S TEMP S M W T F T OVR UNOCC Which mode is selected See page 3 Menu Item Override Menu Item Override Menu Item...

Page 18: ...nOcc 1 5 00 pm Occ 2 10 30 pm UnOcc 2 Friday 6 00 am Occ 1 8 30 am UnOcc 1 5 00 pm Occ 2 11 30 pm UnOcc 2 Saturday 8 00 am Occ 1 11 30 pm UnOcc 1 Null Occ 2 Null UnOcc 2 Schedule P 5 Day Time Temperat...

Page 19: ...when powered down for up to 10 years Battery backup Maintains clock operation for 24hrs when powered down Dial Switch Settings Heating Curve 0 4 to 3 6 Minimum Off 80 to 170 F Off 27 to 77 C Boiler D...

Page 20: ...antability and fitness for a particular purpose shall not extend beyond 24 months from the date of invoice or 12 months from the date of installation of the product whichever occurs first Replacements...

Reviews: