Tekmar Eight Stage Boiler Control 258 Data Brochure Download Page 19

Technical Specifications

Dimension (h x w x d)

— 6-5/8" x 7-9/16" x 2-13/16" (170 x 193 x 72mm)

Weight

— 2.9 lbs (1.3 Kg)

Ambient

— 30 to 120

°

F (0 to 50

°

C), < 95% RH non-condensing

Power supply

— 24Vac 

±

 10%, 60Hz, 5VA class II

— For alternate power supplies (50Hz or 24Vdc), contact the factory

Relay capacity

— 9 x SPST, 24Vac, 10 Amps – 1 x SPDT, 24Vac, 8 Amps

Sensors

— Outdoor Sensor 070, Sensor 071; Accurate with up to 500 feet (150m) 18AWG cable

Control accuracy (temp.)

±

 1

°

F (

±

 0.5

°

C)

Control Processing

— PID algorithm

This electronic control does not exceed the Class B limits for radio noise emissions from digital apparatus as set out in the Radio Interference Regulations of the
Canadian Department of Communications.  Le présent numérique n'émete pas de bruits radioeléctriques dépassant les limites applicables aux appareils numériques de
Classe B prescrites dans le réglement sur le brouillace radioeléctrique édicté par le Ministére des Communications du Canada.

Features

18 Indicator lights

— Power, Heat Demand, Setpoint, WWSD, Minimum, Comb. air, Pump, Actual Supply, Target Supply

Stage 1, Stage 2, Stage 3, Stage 4, Stage 5, Stage 6, Stage 7, Stage 8, Test

Comb. air damper output

— Isolated SPST relay contacts close before first boiler is fired (60 sec.)

Pump output

— Isolated SPST relay contacts close when heating or setpoint is required

Stage 1 to 7 output

— Isolated SPST relay contacts close to operate each stage

Stage 8

— Isolated SPDT relay contacts. N.O. contacts close to operate Stage 8

Test button

— Initiates and controls pre-programmed test run

Error message display

— Sensor faults are indicated by flashing light code

Setback timer/clock

— Programmable

Memory backup

— Retains programmed information and boiler run times when powered down for up to 10 years

Battery backup

— Maintains clock operation for 24hrs when powered down

Dial & Switch Settings

Heating Curve

— 0.4 to 3.6

Minimum

— Off, 80 to 170

°

F (Off, 27 to 77

°

C)

Boiler Differential

— 2 to 42

°

F (1 to 23

°

C)

Stage 1 to 8 switches

— To switch each Stage off or into operating mode

Rotate switch

— To allow boilers to rotate firing sequence based on hours of use (re-ranks after 48 hrs of use)

Fixed lead switch

— Configures Stage 1 to be first/on first/off regardless of hours of use

Fixed last switch

— Configures last Stage to be last on first off regardless of hours of use

Lo/Hi fire switch

— Configures Stages to fire and rotate as pairs

Timer switch

— Setback input from internal timer or external source

Heat Demand switch

— External 24Vac signal or permanent internal signal

Setpoint/Reset switch

— Control operates in reset or setpoint mode

Keypad Programming

Occupied room temperature

— 35 to 105

°

F (2 to 41

°

C)

UnOccupied room temperature

— 35 to 105

°

F (2 to 41

°

C)

Occupied Setpoint temperature

— 70 to 248

°

F (21 to 120

°

C)

UnOccupied Setpoint temperature — 70 to 248

°

F (21 to 120

°

C)

Override temperature

— Setpoint or Room temperature ranges depending on mode

Setback schedules

— 6 pre-programmed, 1 programmable — 7 day, 2 events per day

Display Readouts

Desired Occ.temperature

— 35 to 105

°

F (2 to 41

°

C)

Desired UnOcc. temperature

— 35 to 105

°

F (2 to 41

°

C)

Desired Occ. Setpoint temp.

— 70 to 248

°

F (21 to 120

°

C)

Desired UnOcc. Setpoint temp.

— 70 to 248

°

F (21 to 120

°

C)

Override temperature

— Setpoint or Room temperature ranges depending on mode

Actual Supply temperature

— -67 to 293

°

F (-55 to 145

°

C)

Outdoor temperature

— -67 to 293

°

F (-55 to 145

°

C)

Target supply temperature

— 35 to 248

°

F (2 to 120

°

C)

Boiler accumulated running times

— 0 to 999,999 hrs. for each stage

Setback schedules

— 6 pre-programmed, 1 programmable — 7 day, 2 events per day

Time of Day/Day of Week

— 12 hr., 7 day clock

19

Technical Data

Summary of Contents for Eight Stage Boiler Control 258

Page 1: ...mand Minimum WWSD Pump Stage 1 Stage 2 Comb air Stage 3 Stage 6 Stage 5 Stage 8 Stage 7 Stage 4 Menu Item Override Setpoint Actual Supply Target Supply S PRGM TEMP F C TIME USE AMPM UNOCC OVR M T W T...

Page 2: ...ugh water to keep the room temperature warm particularly during the colder weather If the Heating Curve selected is too high the supply water will be too hot for the conditions and the building will o...

Page 3: ...ntrol The effect of the Integral function can also be easily viewed by not allowing a rise in supply temperature when the control asks for more heat The displayed target temperature will show a slow b...

Page 4: ...allow Heating Curve operation System pump light on the system pump relay is on closing the contacts between terminals System Pmp 3 4 Comb air light on the combustion air relay is on closing the contac...

Page 5: ...e Occupied room temperature setting the control enters WWSD When switched into Unoccupied mode the UNOCC display element will replace the OCC display element and the control will switch from operating...

Page 6: ...e Stage and Comb air lights will be shut off with the boilers and combustion air damper The control will continue to cycle the boilers and combustion air damper to maintain the supply at the target te...

Page 7: ...lighter guage wire is too fragile and may also contribute too much resistance to the circuit Power should not be applied to any of the wires during this rough in wiring stage Step Four Electrical con...

Page 8: ...nals Heat Dem 5 and 6 When 24Vac is applied to these terminals the control will recognize a call for heat from the system DIP switch must be set to Reset If a 24Vac Setpoint Demand signal is used aqua...

Page 9: ...powered up the combustion air damper should operate If it does not come on check the circuit wiring for errors and ensure that it is powered up and the voltage is correct Check the devices in the cir...

Page 10: ...e Heating Curve use the following formula Outdoor air temperature Supply water temperature 50 10 30 1 10 12 10 F 23 C 110 43 70 21 70 21 90 32 210 99 170 77 150 65 130 54 190 88 3 6 3 0 2 4 2 0 1 6 0...

Page 11: ...w Domestic Hot Water boilers to be switched over to assist the heating boilers during peak load times Int timer switch The 258 control has an internal timer programmed using the LCD display and keypad...

Page 12: ...tback and delivering cold water to the boilers increased load Typically this will cause many or all of the boilers to be staged on with minimum delay which is the correct control action for the situat...

Page 13: ...ustion air damper will remain open After the 5 minutes the control will automatically exit the test routine and enter the normal operating mode If there is no Heat Demand the control will not allow a...

Page 14: ...ply temperatures and the LED system status lights display the operation of the various system components A competent troubleshooter can locate system faults without having to go any further than obser...

Page 15: ...tual Supply Target Supply F S TEMP OCC S M W T F T Auto Stage 1 2 3 4 5 6 7 8 Perm Demand Ext timer Fixed last Int timer Lo Hi fire Fixed lead Rotate Off 1 2 3 4 5 6 7 8 9 External Demand Off 1 2 3 4...

Page 16: ...ress or to change the day pointer PROGRAM MENU VIEWING Must be set to Int timer Auto 1 2 3 4 5 6 7 8 Perm Demand Ext timer Int timer Off 1 2 3 4 5 6 7 8 9 External Demand Off 1 2 3 4 5 6 Stpnt Reset P...

Page 17: ...button when the control is showing a fixed display Setpoint Actual Supply Target Supply F S TEMP S M W T F T OVR UNOCC Which mode is selected See page 3 Menu Item Override Menu Item Override Menu Item...

Page 18: ...nOcc 1 5 00 pm Occ 2 10 30 pm UnOcc 2 Friday 6 00 am Occ 1 8 30 am UnOcc 1 5 00 pm Occ 2 11 30 pm UnOcc 2 Saturday 8 00 am Occ 1 11 30 pm UnOcc 1 Null Occ 2 Null UnOcc 2 Schedule P 5 Day Time Temperat...

Page 19: ...when powered down for up to 10 years Battery backup Maintains clock operation for 24hrs when powered down Dial Switch Settings Heating Curve 0 4 to 3 6 Minimum Off 80 to 170 F Off 27 to 77 C Boiler D...

Page 20: ...antability and fitness for a particular purpose shall not extend beyond 24 months from the date of invoice or 12 months from the date of installation of the product whichever occurs first Replacements...

Reviews: