Tekmar Eight Stage Boiler Control 258 Data Brochure Download Page 12

12

Test button

The control can be made to cycle through a test routine whenever the Test button is pushed. The
test can be halted at certain times by pushing the button a second time. For details of the test
routine, refer to the description starting on the next page.

Test

Boiler Differential and Time Delay

The Boiler Differential adjustment sets how much the actual
supply water temperature may deviate from the desired tempera-
ture before stages are turned on or off, and is determined by the
flow rate past the supply sensor relative to the amount of heat
produced by each stage. To prevent short operating cycles of the
boilers the control has a delay of at least 1 minute between firing
cycles. On an installation where flow rates are known, the Boiler
Differential can be calculated as follows:

Desired temperature
this example
160

°

F(71

°

C)

T

emperature

W

armer

Cooler

Time

Differential

this example 

10

°

F(5

°

C)

165

°

F(74

°

C)

155

°

F(68

°

C)

Te

m

p

e

ra

tu

re

 fa

ll

Staging

OFF             ON

Te

m

p

e

ra

tu

re

 r

is

e

Boiler Differential =

For example:

=

10

°

F (6

°

C)

Btu/hr

US GPM x 500

100,000 Btu/hr

20 US GPM x 500

Trial setting = 22

°

F if

flow rates are unknown

22

°

F

2

42

Boiler 

Differential

All boilers will eventually turn on when the temperature falls 

and stays 5

°

F (3

°

C) below the desired temperature. Delays of 1 to

5 minutes for staging on depend on the degree of control error (P+I+D). As the temperature rises to within the differential range,
no boilers are staged on or off. All boilers will eventually turn off when the temperature rises 

and stays 5

°

F (3

°

C) above the desired

temperature. Delays of 8 seconds to 3 minutes for staging off depend on the degree of control error.

Setting a boiler differential for modular boilers is often complicated
by the fact that flow rates and heating loads may vary widely, and
at times boiler outputs may not be balanced to the load. Observing
the "Target Supply" fixed display while the boilers are staging can
assist the user in understanding system flow and boiler problems.
The ideal control reaction occurs when the target supply tempera-
ture remains constant or only changes slightly during the staging
process, indicating a well balanced and constant – or slowly
changing – load vs. output in the system.
If the target supply temperature decreases 

rapidly when a boiler

comes on, it indicates a heavy derivative action by the control in
response to a rapid supply temperature increase. This type of
action typically indicates a condition where the boiler output is far
in excess of the load, a situation that is usually the result of a system
that is operating with only a few zones open (decreased load).
Setting a wider differential and ensuring a minimum fixed load (wild
loops) can help minimize this problem.
If the target supply temperature increases 

rapidly, it indicates a

heavy derivative action by the control in response to a rapid load
increase. This type of action typically indicates situations where the
load is not finely divided (a few large zones) and is usually the result
of one large zone opening – or a system coming out of setback –
and delivering cold water to the boilers (increased load). Typically,
this will cause many or all of the boilers to be staged on with
minimum delay, which is the correct control action for the situation.

If the load fluctuates rapidly and repeatedly from heavy to light,
some instability may result in the staging process as the control
tries to bring on many boilers at once and then shut them off again
when the load suddenly decreases. The target temperature will be
constantly increasing and decreasing. Setting a wider differential
will help to stabilize the control action in many of these cases.
If the target supply temperature slowly and continually climbs, it
indicates that the supply temperature is not rising to the target
temperature. The control will continue to request more and more
boilers until the supply temperature rises sufficiently to reduce the
control error. This problem is called "Reset Windup" and can occur
in systems where: (a) the boilers are undersized, (b) flow is
interrupted – 

without removing the heat demand – to the point

where the supply sensor cannot detect the supply temperature
increase, or (c) where the supply sensor is incorrectly placed – ie.
on the wrong pipe or on the 

return of a system with very long runs.

The problem must be identified and corrective action taken.
If the target supply temperature slowly and continually decreases
after the boilers have been shut down, it indicates that the supply
temperature is hotter than the target temperature. This can happen
in systems with high mass boilers where the flow has been stopped
without using the heat demand input to the control, and convection
from the still hot boiler continues to heat the supply sensor. If the
heat demand input is used to shut the system down, the control will
ignore the sensor reading during the off cycle.

Overheating of buildings in warm weather will occur where minimum boiler temperatures are
required, unless the building has either a mixing system to reduce system supply water
temperatures to below boiler minimums, or some sort of room temperature control and zoning
system. Zone controls from tekmar, when used in these applications, will provide room
temperature feedback information to this control, allowing it to shift the heating curve for
maximum comfort and energy savings.

Typical Minimum Boiler Operating Temperatures:  • Steel Tube Boilers …140

°

 to 180

°

F (60

°

to 82

°

C) • Cast Iron Boilers …130

°

 to 150

°

F (54

°

 to 66

°

C) • Copper Tube Boilers …105

°

 to

150

°

F (41

°

 to 66

°

C) • Condensing or Electric Boilers …Off

Note: If the control is being operated in the setpoint mode and a boiler minimum setting is
selected, the user will be unable to program a setpoint lower than the minimum temperature
plus 1/2 of the Boiler Differential setting. If the minimum dial is set  higher than the setpoint
less 1/2 the Boiler  Differential, the setpoint will automatically be raised as the dial is turned
up. If the dial is then turned back down, the setpoint will have to be re-programmed.

Outdoor air  temperature

Supply water temperature

50

(10)

30

(-1)

10

(-12)

-10

°

F

(-23)

°

C

110
(43)

70

(21)

70

(21)

90

(32)

210
(99)

170 
(77)

150 
(65)

130 
(54)

190
(88)

3.6 3.0 2.4 2.0

0.8

0.4

1.0

0.6

90

(32)

50

°

F

(10)

°

C

Heating

Curve

1.2

Minimum Supply

Setting 130

°

F

WWSD

Point

70

°

F

1.6

Summary of Contents for Eight Stage Boiler Control 258

Page 1: ...mand Minimum WWSD Pump Stage 1 Stage 2 Comb air Stage 3 Stage 6 Stage 5 Stage 8 Stage 7 Stage 4 Menu Item Override Setpoint Actual Supply Target Supply S PRGM TEMP F C TIME USE AMPM UNOCC OVR M T W T...

Page 2: ...ugh water to keep the room temperature warm particularly during the colder weather If the Heating Curve selected is too high the supply water will be too hot for the conditions and the building will o...

Page 3: ...ntrol The effect of the Integral function can also be easily viewed by not allowing a rise in supply temperature when the control asks for more heat The displayed target temperature will show a slow b...

Page 4: ...allow Heating Curve operation System pump light on the system pump relay is on closing the contacts between terminals System Pmp 3 4 Comb air light on the combustion air relay is on closing the contac...

Page 5: ...e Occupied room temperature setting the control enters WWSD When switched into Unoccupied mode the UNOCC display element will replace the OCC display element and the control will switch from operating...

Page 6: ...e Stage and Comb air lights will be shut off with the boilers and combustion air damper The control will continue to cycle the boilers and combustion air damper to maintain the supply at the target te...

Page 7: ...lighter guage wire is too fragile and may also contribute too much resistance to the circuit Power should not be applied to any of the wires during this rough in wiring stage Step Four Electrical con...

Page 8: ...nals Heat Dem 5 and 6 When 24Vac is applied to these terminals the control will recognize a call for heat from the system DIP switch must be set to Reset If a 24Vac Setpoint Demand signal is used aqua...

Page 9: ...powered up the combustion air damper should operate If it does not come on check the circuit wiring for errors and ensure that it is powered up and the voltage is correct Check the devices in the cir...

Page 10: ...e Heating Curve use the following formula Outdoor air temperature Supply water temperature 50 10 30 1 10 12 10 F 23 C 110 43 70 21 70 21 90 32 210 99 170 77 150 65 130 54 190 88 3 6 3 0 2 4 2 0 1 6 0...

Page 11: ...w Domestic Hot Water boilers to be switched over to assist the heating boilers during peak load times Int timer switch The 258 control has an internal timer programmed using the LCD display and keypad...

Page 12: ...tback and delivering cold water to the boilers increased load Typically this will cause many or all of the boilers to be staged on with minimum delay which is the correct control action for the situat...

Page 13: ...ustion air damper will remain open After the 5 minutes the control will automatically exit the test routine and enter the normal operating mode If there is no Heat Demand the control will not allow a...

Page 14: ...ply temperatures and the LED system status lights display the operation of the various system components A competent troubleshooter can locate system faults without having to go any further than obser...

Page 15: ...tual Supply Target Supply F S TEMP OCC S M W T F T Auto Stage 1 2 3 4 5 6 7 8 Perm Demand Ext timer Fixed last Int timer Lo Hi fire Fixed lead Rotate Off 1 2 3 4 5 6 7 8 9 External Demand Off 1 2 3 4...

Page 16: ...ress or to change the day pointer PROGRAM MENU VIEWING Must be set to Int timer Auto 1 2 3 4 5 6 7 8 Perm Demand Ext timer Int timer Off 1 2 3 4 5 6 7 8 9 External Demand Off 1 2 3 4 5 6 Stpnt Reset P...

Page 17: ...button when the control is showing a fixed display Setpoint Actual Supply Target Supply F S TEMP S M W T F T OVR UNOCC Which mode is selected See page 3 Menu Item Override Menu Item Override Menu Item...

Page 18: ...nOcc 1 5 00 pm Occ 2 10 30 pm UnOcc 2 Friday 6 00 am Occ 1 8 30 am UnOcc 1 5 00 pm Occ 2 11 30 pm UnOcc 2 Saturday 8 00 am Occ 1 11 30 pm UnOcc 1 Null Occ 2 Null UnOcc 2 Schedule P 5 Day Time Temperat...

Page 19: ...when powered down for up to 10 years Battery backup Maintains clock operation for 24hrs when powered down Dial Switch Settings Heating Curve 0 4 to 3 6 Minimum Off 80 to 170 F Off 27 to 77 C Boiler D...

Page 20: ...antability and fitness for a particular purpose shall not extend beyond 24 months from the date of invoice or 12 months from the date of installation of the product whichever occurs first Replacements...

Reviews: