20
TS1001 Touch Screen Arming Station Installation Manual
3.
Use the USB cable to connect the computer to RAS’s USB port (Figure 4 on
page 5, item 5).
The first time you connect a RAS to the computer’s USB port, the Found New
Hardware Wizard may display. If the Found New Hardware Wizard does not
display, go directly to step 7.
4.
If the wizard asks “Can Windows connect to Windows Update to search for
software?”, click to select the “No, not this time” radio button, and then click
Next.
5.
If the wizard asks “What do you want the wizard to do?”, click to select the
“Install from a list or specific location” radio button, and then click Next.
6. Click to select the
“Search for the best driver in these locations” radio button,
and then browse to include the location of the Tecom Firmware Loader
application in the search (for example, C:\Program Files\Tecom Firmware
Loader\inf_driver).
7. Run Tecom Firmware Loader (for example, double-click the file C:\Program
Files\Tecom Firmware Loader\tecom-fw-loader_Vn.n.exe).
When you run it will tell you if
the device is ready, otherwise you can’t select a
file.
8.
Click Select File… and then browse to the location of the firmware upgrade
file on your computer (named, for example, ts_ras.6437.img). Select the file
and then click Open.
9.
Click Program File… to update the RAS’s firmware. The process will take
several minutes. The percentage completion displays at the bottom of the
window. When finished, a
“Programming is complete” message displays.
10. Remove the USB cable from the RAS.
11. Disconnect the
RAS’s power supply.
12. Reconnect power to the RAS. The three keys will blink rapidly for a few
moments, and then the RAS will restart.