8
TS1001 Touch Screen Arming Station Installation Manual
Tamper switch
Ensure the tamper switch is sealed when mounting the RAS.
The tamper switch (Figure 3 on page 5, item 3) must be sealed (or the tamper
function deactivated) to avoid
“RAS Tamper” messages during operation.
Note:
If sealing the tamper switch is not practicable you may need to deactivate
the tamper function. See
“2-Tamper Control” on page 14 for details.
DIP switches
An eight-segment DIP switch is located on the PCB (see Figure 4 on page 5,
item 2) and is used for setting the RAS address and the LAN termination (TERM)
condition.
The seventh segment of the DIP switch is for factory test mode and must always
be set to OFF.
LAN address
RASs must be addressed in the range 1 to 16. Use the first four segments of the
DIP switch to set the LAN address. Refer to Table 2 below.
Table 2: RAS address DIP switch settings
LAN
Address
Polled as
SW1
SW2
SW3
SW4
LAN 1
RAS 01
RAS 01
O
O
O
O
LAN 1
RAS 02
RAS 02
I
O
O
O
LAN 1
RAS 03
RAS 03
O
I
O
O
LAN 1
RAS 04
RAS 04
I
I
O
O
LAN 1
RAS 05
RAS 05
O
O
I
O
LAN 1
RAS 06
RAS 06
I
O
I
O
LAN 1
RAS 07
RAS 07
O
I
I
O
LAN 1
RAS 08
RAS 08
I
I
I
O
LAN 1
RAS 09
RAS 09
O
O
O
I
LAN 1
RAS 10
RAS 10
I
O
O
I
LAN 1
RAS 11
RAS 11
O
I
O
I
LAN 1
RAS 12
RAS 12
I
I
O
I
LAN 1
RAS 13
RAS 13
O
O
I
I
LAN 1
RAS 14
RAS 14
I
O
I
I
LAN 1
RAS 15
RAS 15
O
I
I
I
LAN 1
RAS 16
RAS 16
I
I
I
I
LAN 2
RAS 01
RAS 65
O
O
O
O
LAN 2
RAS 02
RAS 66
I
O
O
O
LAN 2
RAS 03
RAS 67
O
I
O
O
LAN 2
RAS 04
RAS 68
I
I
O
O
LAN 2
RAS 05
RAS 69
O
O
I
O