Tecnoware Power Systems
EVO STAR 10-50
9
2
HANDLING, STORING AND POSITIONING
2.1
HANDLING
1.
Remove the screws which fasten the machine to the pallet (Picture 3).
2.
Remove the wooden pallet by using a lift truck and carefully place it on the floor (Picture 4).
3.
For floor handling you will only need a transpallet with a suitable loading capacity.
Picture 3
2.2
U.P.S. STORAGE
2.2.1
U.P.S.
If you need to store the UPS this must be protected from dust and dirt (even if it is well
packaged). It must not be exposed to the inclemency of the weather and the room shouldn’t
be too humid (humidity below 90% non-condensing), nor should the UPS be exposed to
sources of heat; room temperature should be b1 e +40°C.
2.2.2
BATTERY CABINETS
If you need to store a complete battery cabinet, you should respect all the conditions
mentioned in the previous paragraph. You should also remember that battery discharge over
time, even when not in use, therefore
it is necessary to recharge them every 4 months.
In any case, you must follow the manufacturers’ indications to store the batteries.
Non-compliance with these indications can cause an efficiency decrease and a
shorter life of the storage batteries.