RELAY BOARD
The relay board is an interface system with the user on which it is possible to know the status of
the UPS via eight deviators controlled by the system, one of which standard and the other seven
optional. These contacts are normally used for turning on the acoustic and visual signalling systems,
depending on specific events. The types of relays used allow for connecting the users in operation
up to 250V with alternate current, with a maximum input of 10A.
An alarm can be associated with each relay (see table B1), otherwise the standard setting can be
maintained. In the event of having to modify the alarm/relay match-up please contact a technician.
The position of this board will change according to the model chosen, however once removed,
the second access will always be visible and accessible to the user.
RELA
Y
Associated status
( Standard )
Central
contact
Available
contacts
Configurable alarm statuses
1 N.C.
Current >150%
Current >125%
A
RECTIFIER OK
2
3 N.O.
Frequency alarm
Out-of-step alarm
4 N.C.
Phase zero alarm
Inverter V incorrect
B
INVERTER ON (optional)
5
6 N.O.
IGBT desaturation
Inverter on
7 N.C.
Generic alarm
VDC < 350V
C
LOAD ON RESERVE
(optional)
8
9 N.O.
I out > I rated
Power supply alarm
10 N.C.
Error in DC Link
Pretemp. alarm
D
LOAD ON INVERTER
(optional)
11
12 N.O.
Inverter temp. high
OUT voltage Ok
13 N.C.
Load on reserve
Load on Inverter
E
PRETEMP. ALARM.
(optional)
14
15 N.O.
Reserve frequency OK
Reserve voltage OK
16 N.C.
Incorrect reserve cycle
Rectifier V OK
F
INVERTER TEMP. HIGH
(optional)
17
18 N.O.
Rapid load
Rectifier OK
19 N.C.
Incorrect rectifier cycle
Rectifier high temp
G
VDC < 350V (optional)
20
21 N.O.
Relay board jumper
Battery disconnecting
switch
22 N.C.
By-Pass Disconnecting
switch
Output disconnecting
switch
H
CURRENT > 125%
(optional)
23
24 N.O.
Reserve Disconnecting
switch
Rectifier disconnecting
switch
CN
2
CN3
LEDs
Jumper
1
2
A
B
C
D
E
F
G
H
Terminal board
era
CN1
Figure 16