Tecnoware Power Systems
EVO STAR 10-50
49
Output voltage
distortion
100% linear load
2% TDH max
100% not linear load
(IEC62040)
5% TDH max
Crest factor
3:1 load 80%
Voltage symmetry
100% balanced load
120+/-1%
100% unbalanced load
(80%-0-80%)
120+/-2%
Output frequency
From internal quartz
50/60 Hz +/- 0,01%
Frequency Windows
+/-5%
Overloading (on inverter)
125% for 10 min., 125%-150%for 60sec.
Short circuit (on inverter)
150% of nominal current for 60 sec within limitation system
Static bypass
Configuration
Only one input, dual input optional
Voltage windows
+/-10% of nominal system voltage (adjustable)
Overload (on bypass)
125% continuous, 200% for 5 minutes, 1000% for ½ cycle
Manual bypass switch
Standard
Serial
Option RS232 with Megatec protocol (only with micro control
board)
Contact relay
One, optional board with 8 programmable relays (only with micro
control board)
Chart 8